Can I set the PV display to -100 with 20 mA input, and to 0 with 4 mA input?

In this case, 20 mA is the minimum value of PV input, and 4 mA is the maximum. In the setup parameter PV menu, set RH=4.00 and RL=20.00 (the input range maximum and minimum values). For the PV input scale max, min, and decimal place, set SH=0, SL=-100, and SDP=0. SH must be greater than SL.

Productos y Soluciones Relacionadas

  • UM33A

    The UM33A is a digital indicator with alarms provides up to 9 alarms outputs and input correction function (PV bias, Polygonal line approximation, polygonal line bias). Also, 24 VDC sensor power supply is available as an option.

    Leer Más
  • UP35A/UP32A

    The UP35A is a program controller with available 4 patterns and 40 segments (max.) and multi-channel contact I/O. It also includes a ladder sequence function. The UP32A is a compact program controller with up to 4 patterns and 40 segments available. It also includes a ladder sequence function.

    Leer Más
  • UP55A

    The UP55A is a newly-released 1/4 DIN sized program controller provides up to 30 program patterns, and simultaneous monitoring of 8 PV events, 16 time events, and 8 alarms. Also a ladder sequence function is included as standard.

    Leer Más

Top