How can I output the UT32A's measured values at 4–20 mA to 2 outputs?

Use transmission output and control output.
The following are setting examples.
IN=K1(-270.0–1370.0), RH=1000.0,RL=0.0, (in the PV setup parameter)
OT=00.00 (in the OUT setup parameter)
RTS=PV1,RTH=1000.0,RTL=0.0
o1RS=PV1,O1RH=1000.0.O1RL=0.0

Related Products & Solutions

  • UT35A/UT32A

    The UT35A and UT32A temperature controllers employ an easy-to-read, 14-segment large color LCD display, along with navigation keys, thus greatly increasing the monitoring and operating capabilities. A ladder sequence function is included as standard. The short depth of the controller helps save instrument panel space. The UT35A/UT32A also support open networks such as Ethernet communication.