In the setup parameter ALM menu, set the AL1.S parameter to 4353 (AL01_L1).
[Supplement]
4321(ALM1) is the alarm status of ON when an alarm occurs, and OFF when normal.
4353(AL01) is the alarm status determined by applying the settings for alarm energize/de-energize, latch operation, and contact type to 4321(ALM1).
Related Products & Solutions
-
UP35A/UP32A
The UP35A is a program controller with available 4 patterns and 40 segments (max.) and multi-channel contact I/O. It also includes a ladder sequence function. The UP32A is a compact program controller with up to 4 patterns and 40 segments available. It also includes a ladder sequence function.
-
UP55A
The UP55A is a newly-released 1/4 DIN sized program controller provides up to 30 program patterns, and simultaneous monitoring of 8 PV events, 16 time events, and 8 alarms. Also a ladder sequence function is included as standard.