ADMAG AXR

The ADMAG AXR two-wire, loop-powered magnetic flow meter can be installed in a two-wire system. The maximum power consumption of the AXR is 0.3W, 40 times less power draw than a traditional magnetic flow meter, resulting in CAPEX and OPEX savings.

The ADMAG AXR is the world's first two-wire magnetic flow meter that employs the fluid noise-free "Dual Frequency Excitation Method" for excellent stability for instrumentation.

Details

What Is the The ADMAG AXR?

2-wire Power Loop

An extra AC power supply is not necessary. 2-wire loop powered performance allows direct connection to DCS I/O card possible, allowing for real cost reductions.

  • Reduced CAPEX and OPEX on site.
  • Power consumption reduced by 40% compared to a typical 4-wire magnetic flowmeter.
  • Annual CO2 emissions can be reduced from approximately 60 kg to 1.2 kg (compared to a standard 4-wire magnetic flowmeter).

Dual Frequency Performance

Yokogawa’s unique and advanced excitation method, "Dual Frequency Excitation," achieves stable measurement, zero stability and quick response times. The exclusive technology for stable and reliable measurement on your site.

Noise Reduction Technology

Flow noise reduction is further achieved by incorporating smooth mirror finished PFA liners and special surface finished electrodes. This is further enhanced with aligned super high density coils that generate a stronger magnetic field.

SIL2 Certified

Yokogawa believes safety should not be an option; it should be standard in all modern products. AXR is the first 2-wire magmeter of SIL2 Safety Integrity Level (IEC 61508) certified. AXR is capable of SIL2 single use and SIL3 redundant use, as standard.

Parameter Operation

AXR has magnet switches for parameter setting. Users can access the functions without removing the case cover in hazardous, humid, and dusty environments.

Adhesion Diagnostic Level Function

The electrode is one of the most important parts of a magnetic flow meter. Only ADMAG flow meters have "Adhesion Diagnostic Level Function". It diagnoses the condition of electrode surface and indicates the adhesion/coating in 4 levels. Users can change the detection level (threshold) depending on each individual process condition. This allows for predictive maintenance and reduced operating costs.

Alarm Indication

ADMAG AXR employs a full-dot matrix LCD indicator. It can display up to 3 lines as required by the user and is available in multiple languages. If an alarm is triggered, a clear message is displayed along with a solution.

High Accuracy

The ADMAG AXR performs 0.5% of rate under normal flow rate conditions.

Structure Integral flow meter
Excitation Method Dual frequency excitation
Nominal Pipe Size
[Unit : mm (approx. inch)]
General-purpose use: 25 (1.0) to 200 (8.0)
Explosion proof Type: 25 (1.0) to 200 (4.0)
Supply Voltage Operating voltage range 14.7 to 35 V DC Two-wire system
Output Signals Current output
Digital output (One output can be selected from pulse, alarm or status outputs.)
Electrode Material Stainless steel-JIS SUS316L (AISI 316L SS/EN 1.4404 equivalent), Hastelloy C276 equivalent, Tantalum, Platinum-iridium
Fluid Temp. - 40 to 130 deg.C (-40 to 266 deg.F) [ depends on model type ]
Ambient Temp. - 40 to 55 deg.C (-40 to 131 deg.F)
Accuracy 0.5% of rate (Note 1)
[ depends on nominal pipe size and fluid condition ]
Fluid Conductivity 10 micro-S/cm or larger
[ depends on nominal pipe size and fluid condition ]
Lining Fluorocarbon PFA (Mirror-finished lining surface) (Note 2)
Lay Length
[Unit : mm (approx. inch)]
Lay length code 1: Wafer ; size 80 (3.0) to 200 (8.0), Flange ; size 25 (1.0) to 200 (8.0)
Lay length code 2: Wafer ; size 25 (1.0) to 200 (8.0)
Indicator Full dot-matrix LCD
Operational Switch 4 magnet switches (including push switches)
Self Diagnosis Electrode adhesion diagnosis, Coil open, etc.
Alarm Message Alarm message with countermeasure is indicated
( English, German, French, Italian, Spanish, Japanese )
Options Direction change of the electrical connection, Special Gaskets,

* Please refer to General Specifications in detail.

Note 1: The accuracy of a product before shipment is defined as totalized value at the result of calibration test in our water actual flow test facility.

Note 2: Mirror finished PFA lining is standard for size 25 to 100 mm (1 to 4 in.) and optional for size 150 to 200 mm (6 to 8 in.) specified by optional code PM.

Resources

Overview:

The ADMAG AXR employs the patented “Dual Frequency Excitation Method.” This unique technology combines the best properties of low-frequency excitation to enable a stable measurement and high-frequency excitation to deliver excellent noise immunity. As a result, the AXR can suppress process-generated noise to secure zero stability without sacrificing fast response time. In addition, the AXR achieves the same level of noise immunity as a 4-wire circuit under varying fluid conditions and delivers the performance necessary to meet the requirements for control loop applications.

Overview:

The pulp and paper industry holds some of the most aggressive and challenging applications for magmeters. There are corrosive chemicals, high temperatures and pressures, and abrasive slurries. One application which is particularly difficult is the measurement of pulp stock from the digester to the blow tank. Yokogawa can provide one of the most reliable and accurate meters for this application.

Yokogawa Technical Report
Overview:

More than half a century has passed since Yokogawa developed Japan's first magnetic flow meter for industrial use in 1955, and today, Yokogawa's magnetic flow meters are widely used in a variety of applications thanks to features such as low pressure loss and maintenance-free operation due to no obstacles and moving parts in the fluid flowing pipeline.

Overview:

Control Engineering Asia, March 2012

Enabling the operational benefits of two-wire magnetic flow meters while maintaining the performance levels associated with traditional four-wire devices.

ADMAG TI autozero or zero adjustment is carried out to ensure that the output for zero flow is 0% (i.e., 4 mA). Although adjustment to zero is performed at the manufacturing plant prior to shipment, this procedure must be carried out once again follo...
Edition 1
Overview:

ADMAG TI autozero or zero adjustment is carried out to ensure that the output for zero flow is 0% (i.e., 4 mA). Although adjustment to zero is performed at the manufacturing plant prior to shipment, this procedure must be carried out once again following the installation of piping in order to match the magnetic flowmeter to its operating conditions.

The ADMAG AXR two-wire magnetic flowmeter is equipped with magnetic switches on its front fascia that allow for the adjustment of parameters without the need to remove the cover or connect the flowmeter to any external hardware. While most magnets wi...
They help remove stray energy or noise as it builds up in the flow process by grounding it. They can even help protect the magmeter liner from damage in harsher processes.
Edition 1
Overview:

They help remove stray energy or noise as it builds up in the flow process by grounding it. They can even help protect the magmeter liner from damage in harsher processes.

Sizes 25 to 200 mm (1 to 8 in): 10 µS/cm or greater.