The Dynamic Difference
Henk van der Bent, Yokogawa Europe B.V., The Netherlands, looks at enhancing DP based flow measurement with dynamic compensation.
This article describes how a multivariable pressure transmitter with built-in dynamic compensation can compensate for many of the errors and inaccuracies that can occur in differential pressure based flow measurements. It also shows how the built-in computing and communications capabilities of such modern flow meters ensure ease of integration with field device tool (FDT) and device type manager (DTM) tools in monitoring and control systems.
Differential pressure transmitters form the core of many field instrumentation systems, and are widely used to measure the flowrate, pressure and density of liquids, gases and steam, as well as the level of liquid in a tank. Over the years, such transmitters have evolved in response to the demands for increasing accuracy and reliability, as well as enhanced computing and communication facilities, to ease their integration into plant-wide monitoring, control and asset management systems. Not only are field devices required to be more precise and stable: they must also be more intelligent.
Figure 1. The DPharp digital sensor used in the latest generation of multivariable pressure transmitters. |
A major step towards meeting these challenges came with the development of the DPharp digital resonance sensor, which eliminated the error prone A/D converter required by analogue sensors, and provided 'quartz watch' stability with unmatched precision, accuracy, response and repeatability. The combination of a digital sensor with integrated processing circuitry provides sensor diagnostics and high integrity, and allows full digital integration in a Fieldbus based control system.
The DPharp sensor (Figure 1) is an advanced micro-electro-mechanical system (MEMS) based silicon resonant sensor that provides a standard reference accuracy of ±0.04% (optional reference accuracy of ±0.025%) and a 0.1% 10 year stability guarantee. The technology is also inherently failsafe. Moreover, the design of the DPharp sensor allows both differential pressure and static pressure to be transmitted from one transmitter, allowing the basic pressure measurements to be used as the basis of flow and level metering.
The result is a multivariable transmitter which acts as an 'all in one' instrument, integrating the functions of a differential pressure transmitter, a pressure gauge, a thermometer and a flow computer, while featuring high performance and space saving design (Figure 2). The transmitter employs an advanced flowrate calculation method to achieve a mass flow calculation cycle of 100 ms. By adopting a Reynolds number compensation algorithm, all flow calculation parameters are optimised and a mass flow accuracy rate as high as 1% of actual flowrate is achieved.
Figure 2. The Yokogawa EJX910A multivariable pressure transmitter features an integral flow computer. |
The multivariable transmitter is compatible with a wide range of primary devices, including orifice plates, nozzles and venturi tubes, and can be used with various types of fluid, including general fluids, steam and natural gas. Application information, such as the primary devices and fluid data required for mass flow calculation, is input using a mass flow parameter configuration tool that runs on a PC and is downloaded to the transmitter by means of field communication. In operation, the flow meter computes standard volumetric or mass flow from measured differential pressure (DP) and flowing density using actual measured pressure and temperature, unlike standard differential pressure transmitters that assume pressure and temperature, and therefore flowing density, to be constant.
Error sources affecting DP flow measurement
Figure 3 shows the transmitter setup for flow measurement. The basic mass flow equation performed is:
In DP flow measurements, the variation in flowing density is only one of a number of potential sources of error. One source of error is the primary element. The orifice plate is the most widely used primary element, and its accuracy is extensively debated. It is known, however, that its accuracy degrades over time as the plate loses its sharpness. A typical accuracy figure might be 1% of rate. Another source of error is the DP transmitter. This accuracy is expressed as a percentage of upper range value (URV), and is magnified by the square law relationship between flow and differential pressure.
Traditionally, DP based flow meters have featured a 3:1 'turndown'. This is a figure that expresses the range over which the accuracy is perceived to be acceptable: 30 - 100% of flow for a 3:1 turndown. If the accuracy of the DP transmitter is assumed to be ±0.2% URV, at 100% flow the accuracy is ±0.2% plus the error of the plate. At 70% flow (49% DP due to the squarelaw relationship), the accuracy would be ±0.4%; at 50% flow (25% DP) it would be ±0.8%; and at 25% flow (6.25% DP) it would be ±3.2%. The plate adds ±1% over the full range and, when ±2.5% total accuracy is perceived to be acceptable, that accuracy is reached at around 30% flow, hence the 3:1 turn down. Turndown is often increased to 9:1 by using two DP transmitters over the same plate with different ranges, a switching mechanism and a flow computing function.
Today, of course, DP transmitters are much more accurate than ±0.2%. However, the accuracy is still expressed as a percentage of URV, and the squarelaw relationship between flow and DP is still applicable. Nevertheless, one could argue that a turndown of better than 5:1 is not normally achieved. The error due to pressure (±0.5 bar) and temperature fluctuations (±10˚C) in gas or steam flows can easily be of the order of magnitude of ±2%.
Figure 3. Flow measurement setup. |
The flow factor k in the basic formula above is a constant compensating for the differences between theory and real life. It is calculated as part of the orifice calculation, and is valid only for one particular set of operating conditions, making it another potential source of error. It is dependent on the discharge coefficient, the gas expansion factor and velocity of approach factor.
The result of an orifice calculation is the diameter of the hole in relation to the pipe diameter: the so called ß-ratio. When a fluid is flowing through a pipe with an orifice plate, the flowing area reduction is abrupt, causing the smallest flowing area (vena contracta) to be downstream (behind) of the plate. The discharge coefficient (based upon experimental research) compensates for the difference between theory and real life. However, the discharge coefficient is flow profile (Reynolds) dependent and varies with the flow velocity, pipe internal diameter, flowing density and flowing viscosity. In turn, the latter three parameters are affected by flowing temperature.
When a gas or steam flow passes the orifice plate (Figure 4), it is compressed upstream of the plate due to the obstruction caused by the plate. Downstream of the plate it expands again. The gas expansion factor corrects for density differences between the pressure taps, and it depends on the ß-ratio, the isentropic coefficient (correcting for theoretical versus real life expansion), differential pressure and static pressure. Again, temperature has an effect as well. Finally, the velocity of approach factor is dependent on the ß-ratio (d/D), which in turn is dependent on temperature. The pipe and orifice plate material expands or contracts as temperature changes, and the velocity of approach factor corrects for changes in ß-ratio due to temperature fluctuation.
Dynamic compensation
Figure 4. Effects of orifice plate on flow. |
The error in flow factor k increases with decreasing flowrate, significantly contributing to the overall flow meter accuracy. A primary element of a DP based flow meter is sized for one particular set of operating conditions. When in real life the conditions change (lower pressure, higher temperature, lower flowrate etc.) the user would like to recalculate the flowrate/DP relationship for every new set of conditions. This is exactly what the multivariable transmitter is able to do. It corrects for pressure and temperature variations and it can compensate continuously for the effects of changing operating conditions on the flow factor. Using its flow configuration wizard, the transmitter can be set up to act as a flow computing device.
There are two options: basic mode and auto compensation mode. In basic mode, the transmitter only compensates for pressure and temperature fluctuations with a constant flow factor, in much the same way as a standard DP transmitter with a separate flow computer, resulting in a turndown of perhaps 5:1. However, in the auto compensation mode, it dynamically compensates for fluctuating conditions and their effects on the flow factor, reducing the error basically to the uncertainty intrinsic to the primary element. Consequently, the accuracy specification of ±1% of flowrate (assuming the primary element to be ideal) over a 10:1 turndown in flow terms (equivalent to 100:1 turndown in DP terms) is only valid in the auto compensation mode. From the above, it can be seen that this multivariable transmitter breathes new life into existing square-law flow measurements and, with its 10:1 turndown, not only eliminates the need for a separate flow computer, but can replace one or two DP transmitters and a pressure transmitter over the same plate, while achieving good performance over a wide flow range.
Figure 5. The Yokogawa FieldMate™ Advanced portable field device engineering and maintenance tool offers easy configuration and diagnosis of field transmitters. |
This transmitter will measure differential pressures from 1 mbar up to 5 bar, and absolute pressure up to 160 bar. As indicated above, it supports a range of primary flow devices including orifice plates and venturi tubes. The flow computer currently includes a DIPRR (AIChE) physical properties database for 126 fluids and gases, and its compressibility equations meet international standards including the AGA 8 and ISO12213 natural gas equations (either simplified or using the full molecular weight composition method), IAPWS-IF97 formulation for water and steam, or custom compensation based on user defined density and viscosity data.
Configuration through advanced DTM
An important benefit of these advanced transmitters is provided by their advanced communication capabilities, allowing them to interface with other elements of an integrated plant-wide operation. As a result, it is possible to carry out remote configuration and diagnosis using industry standard tools such as FDT/DTM technology. FDT is an open interface specification and a DTM is a 'portable' device (software) application.
FDT/DTM technology is supported by leading suppliers of intelligent devices and control systems. Through DTMs it facilitates the management and configuration of sensors,actuators, flow meters, transmitters and other field devices that are installed at production sites and connected to host control systems and PCs, regardless of the communications protocol used.
Figure 6. The EJX910A DTM graphical user interface (left) with navigation to the add-on flow configuration wizard module (right). |
The DTM for the multivariable transmitter being discussed in this article features an add-on flow configuration wizard. As discussed, this DTM with add-on module can be integrated in any so called FDT frame application. The add-on module not only features the flow configuration wizard configuring the transmitter for a specific flow application: it also contains the fluid property database and features the 'obtain flow coefficient' function where the transmitter calculates the flowrate, flowing density, discharge coefficient etc. on the basis of manually entered values for differential pressure, pressure and temperature to verify the correctness of the flow configuration. Consequently, the latter function drastically reduces the commissioning effort for this type of device.
The use of this technology creates an open environment in control systems and devices such as the multivariable transmitter discussed in this article. The FDT/DTM technology frees users from having to learn configuration methods from different manufacturers and eliminates the constraint of having to install devices from the same manufacturer, allowing more efficient plant operations to be realised.
The system shown in Figure 5 is a configuration and maintenance tool that uses FDT technology to facilitate the configuration and adjustment of field devices in this way, and helps customers to optimise asset availability through improved device control and management. Demand for this kind of configuration software is increasing as field devices become more intelligent and digitalisation of field communications moves forward. By supporting the latest open standards, systems of this type allow users to enjoy the best benefits of intelligent field devices and digital field communications.
Related Products & Solutions
-
EJX910A
Multivariable Pressure Transmitter
-
Mobile Field Device Management (FieldMate)
FieldMate Mobile Field Device Managment
-
Device Smart Communicators
Configure, commission, and troubleshoot from wherever, whenever
Have Questions?
Contact a Yokogawa Expert to learn how we can help you solve your challenges.