Temperature - Can I change the HART revision on a YTA70?

HART Protocol Revision

On a YTA70 with an output signal code of -J, the HART protocol revision of the transmitter can be selectable from HART 5 or HART 7. The HART protocol revision is set and shipped as specified in the order. To change the HART protocol revision after shipment, use an HHC or FieldMate and follow the procedure shown in the Instruction Manual (IM). Please note that selecting HART 5 will change the model code of YTA70-J to YTA70-E on the configuration tool.

On a YTA70 with an output signal code of -E, the HART protocol revision of the transmitter can only be HART 5.

Related Products & Solutions

  • YTA70

    Like the YTA50, the YTA70 is a 2-wire analog temperature transmitter that outputs a simple 4 to 20 mA output that corresponds to the temperature measured. However, it adds HART 5 (Code -E) or selectable HART 5/HART 7 (Code -J) digital communication.