Downstream from a UT with CC-Link communication (the Modbus master), the power to a controller connected via RS485 communication (the Modbus slave) went out. After the power to the controller was restored, communication did not restart. What should I do?

Either set the SCAN parameter, or turn ON the rescan request flag on the PLC side.

Related Products & Solutions

  • UM33A

    Digital Indicator with 9 alarms outputs and input correction function

  • UP35A/UP32A

    Program Controllers with 4 patterns, 40 segments, and ladder sequence functions

  • UP55A

    Program controller with 30 patterns, simultaneous monitoring, and ladder sequence function


Top