I'm writing PID settings via CC-Link communication, but when I send 100 to proportional band P, 10.0 appears on the main unit.

Proportional band P has data of up to 1 decimal point. By contrast, communication data has no decimal point. If you want to write 100.0% to P, send 1000. For differential and integral time, the data has no decimal point.

Related Products & Solutions

  • Advanced Application UT75A

    The UT75A temperature controllers employ an easy-to-read, 14-segment large color LCD display, along with navigation keys, thus greatly increasing the monitoring and operating capabilities. A ladder sequence function is included as standard. The short depth of the controller helps save instrument panel space. The UT75A also support open networks such as Ethernet communication.