There's no output with a thermocouple temperature converter. What should I do?

  1. Check the power supply wiring.
  2. Check whether the power supply voltage meets the specifications.
  3. Confirm that the accessory RJC sensor is connected to the input terminal.
  4. Short the input terminals, then confirm that the output is equivalent to the terminal temperature.
  5. If the output signals is of the current specifications, attach an external 250 Ω resistance and measure the voltage.

Related Products & Solutions

  • JUXTA VJ Series Limit Alarms

    The VJ series limit alarms are compact, plug-in type alarm setting devices with easy-to-use functions. Four models are available: the VJAK for 2-wire system transmitters; the VJHK with DC voltage/DC current inputs; the VJRK with RTD inputs; the VJTK with thermocouple inputs; and the VJUK with universal inputs.

    See More
  • JUXTA VJ Series Signal Conditioners

    Compact size, plug-in style and microprocessor based high performance capabilities (Multi-function types) makes the VJ Series Signal Conditioners an excellent choice for almost every application. Analog output, Hi-Low alarm relay outputs or RS-485 MODBUS communication is available as optional second output.