Using the Event Action Function
Remote input (BCD code) | Formula | Alarm | Internal Switch | Event Action | |||
---|---|---|---|---|---|---|---|
D01 | D02 | D03 | D04 | ||||
o | 101=D01 | H=1 | S01 | Message number 1 | |||
o | 102=D02 | H=1 | S02 | Message number 2 | |||
o | o | 103=D01+D02 | H=2 | S03 | Message number 3 | ||
o | 104=D03 | H=1 | S04 | Message number 4 | |||
o | o | 105=D01+D03 | H=2 | S05 | Message number 5 | ||
o | o | 106=D02+D03 | H=2 | S06 | Message number 6 | ||
o | o | o | 107=D01+D02+D03 | H=3 | S07 | Message number 7 | |
o | 108=D04 | H=1 | S08 | Message number 8 |
Many messages can be output even with a limited number of remote inputs by combining the remote input, computation, alarm, and event action functions.
Eight different messages can be written by combining four remote inputs with eight internal switches.
- D01–D04 are data types added with DXAdvanced, accepting remote input as contact input values.
- S01–S08 are internal switches of functions added with DXAdvanced.
- Alarms are represented with flags (internal switches) rather than relay output, and are set as "events" of the Event Action function.
Industries
-
Iron & Steel
- Iron and steel industry
- Improve quality of products, manufacturing, and operation technologies
- Address environmental and energy-efficiency issues
- Create the ideal plant and evolve for mutual growth
Related Products & Solutions
-
Button Operated DX1000/DX2000
The Daqstation DX1000/2000 series is a data acquisition system with display. Its HMI supports custom graphics for industry applications, audit trail and advanced security conforming to FDA 21CFR Part 11.
Have Questions?
Contact a Yokogawa Expert to learn how we can help you solve your challenges.