Introduction
The detectors used to perform dissolved oxygen (DO) measurement in oxidation ditch type sewage treatment plants tend to become dirty quickly and require frequent cleaning. It has been difficult to remedy this problem inexpensively. One solution that significantly reduces the sensor maintenance workload is the use of float holders. A field test using float holders on the detectors in the FLXA402 dissolved oxygen analyzer system has demonstrated that the sensors could be kept free of heavy dirt accumulation, eliminating the need for maintenance and enabling continuous measurement for long periods of time.
Expected Benefits
- Ensures stable, continuous dissolved oxygen measurement
- Reduces operating cost
- Eliminates the need for manual cleaning
Process Overview
An oxidation ditch is a large circular basin equipped with aerators that is used to remove organic matter and pollutants from sewage through the processes of adsorption, oxidation, and decomposition.
Oxidation Ditch
Solution Details
Measurement System
- Detector: DO30G-NN-50-□□/PN
- Float holders:
Angled type: PB350G-PV-25-NN
Vertical type: PB360G-PV-□5-NN - Converter: FLXA402-□-B-□□-D1-NN-A2-□□-□-□-N-NN
- Terminal box (as needed): WTB10-DO3-NN- □□/□
With the WTB10 terminal box, the sensors and the converter can be up to 50 meters apart.
Field Data
For the onfield test, two detectors were mounted in PB350G angled float holders. One sensor received no maintenance and the other was cleaned every two weeks and calibrated ce a month. This test showed that the readings from the two sensors were nearly identical over a six month period.
Industries
-
Drinking Water Treatment
The goal of drinking water treatment is to produce clean, safe, and potable water that meets regulatory standards and is suitable for drinking and other domestic uses.
-
Wastewater Treatment
The goal of waste water treatment is to produce treated water that meets environmental regulations and can be safely released into bodies of water or reused for purposes like irrigation or industrial processes.
-
Water & Wastewater
All water, regardless of its source, has value. However, with water resources being finite, a focus on "One Water" is necessary to maximize every drop within the water system, ensuring a stable supply of clean and safe water. As we consider current and future needs, planning and implementation are critical for long-term resilience and reliability, meeting both community and ecosystem demands. Yokogawa believes water is a human right for all. Thus, contributing to a sustainable water cycle is one of our Sustainable Development Goals (SDGs).
Related Products & Solutions
-
Dissolved Oxygen Analyzers
Built to withstand the harshest applications
-
Dissolved Oxygen Sensors
Perform liquid process measurement across multiple applications
Have Questions?
Contact a Yokogawa Expert to learn how we can help you solve your challenges.