I wrote the alarm setting values from the UT350 to the UT35A via communication. On the UT350, the alarm setting values were common from 1SP through 4SP, but when updating to the UT35A, what should I do?

Use the GREEN compatible registers DO231 (alarm 1 setting) through DO233 (alarm 3 setting).
Ex.) DO231: A1_G (setting value of alarm 1 for GREEN)

Write the values written to A1_G to A1_L1_1 through A1_L1_4.
A1_L1_1(D2504)
A1_L1_2(D2524)
A1_L1_3(D2544)
A1_L1_4(D2564)

 