Introduction
What is screen differential control? This is a control application commonly found at utility plants located on rivers, lakes and other large bodies of water and at industrial facilities where a large amount of cooling water is used. Screen differential control and monitoring is needed to prevent damage to rotating screens caused by excessive pressure being applied by debris collecting on the screens.
Screen Differential Control
Application
A typical cooling system consists of two or more sets of rotating screens. When the differential across a set of screens reaches 15 cm (7 inches), an alarm is activated. If the differential reaches 25 cm (10 inches), the screens start to rotate and back wash pumps are started initiating a backwash procedure to clean the screens of any accumulated debris.
Differential is measured by monitoring the back pressure created by displacing water in sensing lines using regulated air flow. Lines are located upstream and downstream of each screen.
Upstream and downstream pressures are monitored by a recorder set up to read differential flow. Transmitter outputs are fed into the recorder so operators have tide reference, individual screen differentials with alarms and auto start for wash pumps. These contacts are fed into the screen logic by the recorder alarm option.
Solution
DPharp was recently selected for this application by a major Texas electric utility company when they redesigned their screen differential monitoring and control system. The company selected DPharp over their plant standard because of its ability to withstand plant air applied to sensing lines during blowback operation--without having to be taken out of service, and with no shift in calibration after completion of blowback. Transmitters have been in operation since November of 1996, and plant maintenance personnel are very pleased with their performance.
A simplified screen differential monitoring diagram is shown below. Solenoid valves or a timer are used to initiate automatic blowback operation once a day. DPharp monitors the differential across the rotating screens.
Main Features of DPharp
DPharp |
EJA110A Digital Solution
- Best-in-class performance
- ±0.03% Overpressure calibration protection
- ±0.1% per 5 years long term stability
- 100:1 turndown
- ±0.065% accuracy
EJX110A Premium Value
- ±0.1% per 10 years long term stability
- 200:1 turndown
- Best-in-class high accuracy, 0.04%
- Multi-sensing output
- Multi-variable transmitter as EJX family line-up