AR Series Surge Arresters

The high-performance AR surge arrester absorbs the potential of an inductive lightning surge caused by a lightning discharge to protect electronic instruments. The plug-in arrester consists of a separable main unit and terminal block.

  • Absorbs large surge voltages immediately.
  • Simple circuit configuration and excellent adaptability to a distributed control system.
  • Plug-in connection of the main unit with the terminal block, eliminating concerns about an open-circuit state even if the main unit is removed.
  • Support JIS
    *1: JIS C 5381-21 (category:C1,C2):
          AR-SA, AR-HA, AR-TC, AR-RT, AR-HP, AR-LP, AR-SP, 
          AR-SY, AR1-B2, AR1-D6
    *2: JIS C 5381-1(classⅡ):
          AR-PS, AR-PH, AR-PW

  

Details

Model Description
AR-SA Arrester for Current Signal 
0 to 100 mA DC(12 to 30 V DC signal line)
AR-HA Arrester for Current Signal 
0 to 100 mA DC(48 to 65 V DC signal line)
AR-TC Arrester for Thermocouple (mV signal line)
AR-RT Arrester for RTD and Potentiometer
AR-LP Arrester for 2-wire Pulse Signal (50 V DC or less)
AR-HP Arrester for 2-wire Pulse Signal (90 V DC or less)
AR-SP Arrester for 3-wire Pulse Signal (50 V DC or less)
AR-PS Arrester for Power Supply (100 V AC, 2 A)
AR-PH Arrester for Power Supply (200 V AC, 2 A)
AR-PW Arrester for Power Supply (100 V AC, 20 A)
AR-SY Arrester for Selsyn (90 V AC)
AR1-B2 Arrester for Communication Line (DC to 300 kHz)
AR1-D6 Arrester for Communication Line (DC to 2 MHz)

Kaynaklar

Can I use the AR-RT for the Pt50 Ω RTD?
(ns-faq-ar-16005-select)
Yes.
It uses a zinc oxide varistor.
For converters with an open detection function, during open detection the line-to-line is 40 V, therefore we recommend using the AR-HA (max. continuous line-to-line voltage of 70 V) .
Yes, the AR-LP. It has a rated (load) current of 2 A. Note that this does not support JIS.
Yes, the AR-SA.
You can use the AR-LP. Note that this is not JIS-compliant.
Yes, that is not a problem.
Yes, the AR-LP (for 2-wire pulse signals, 50 VDC or less)
Yes, you need it regardless of the presence or absence of voltage. We recommend the AR-LP.
The “AR-PS” is available. Note that this is not JIS-compliant.
The insulation resistance value at the surge arrester terminal block between the I/O terminals and ground is 100 MΩ or more/500 VDC. The withstand voltage between I/O terminals and ground is 1000 VAC/1 minute (or 1500/1 minute for the AR-PH onl...
Yes. It's the E9731TW. (Please consult with your dealer at the time of purchase.)
They are voltage limiting lightning arresters.
Yes. The adapter for mounting on a DIN rail is an option.
Can I mount on DIN rails?
(ns-faq-ar-16004-select)
A DIN rail adapter can be included with an option when purchasing the surge arrester. If you need to purchase an adapter later, select the AR8-01_DIN rail adapter. ...
There is no load current rating. With this model no load current flows because it is connected in parallel to the load.

İndirilenler

İnsanlarımız, teknolojimiz ve çözümlerimiz hakkında daha fazla bilgi mi arıyorsunuz?

Bizimle İletişime Geçin

En üst