Up to how many SSRs can be connected to the UT?

The UT's voltage pulse specifications are: ON voltage 12 VDC or more; load resistance 600 Ω or more; ON voltage 0.1 VDC or less. For example, in the case of the Omron G3PH (operating voltage DC4-30 V, input current 5 mA or less), up to 4 units can be connected in parallel. To drive an SSR with the UT, use voltage pulse output. Since the current flowing will be 12 V/600 Ω=20 mA, this satisfies the above conditions.

Súvisiace produkty a riešenia

  • Advanced Application UT75A

    The UT75A temperature controllers employ an easy-to-read, 14-segment large color LCD display, along with navigation keys, thus greatly increasing the monitoring and operating capabilities. A ladder sequence function is included as standard. The short depth of the controller helps save instrument panel space. The UT75A also support open networks such as Ethernet communication.

    Vidieť viac
  • Mid-level UT55A/UT52A

    The UT55A and UT52A temperature controllers employ an easy-to-read, 14-segment large color LCD display, along with navigation keys, thus greatly increasing the monitoring and operating capabilities. A ladder sequence function is included as standard. The short depth of the controller helps save instrument panel space. The UT55A/UT52A also support open networks such as Ethernet communication.

    Vidieť viac
  • UT32A-D

    The UT32A-D is a compact digital indicating controller with selectable 2-loop control. It also includes a ladder sequence function.

    Vidieť viac
  • UT35A/UT32A

    The UT35A and UT32A temperature controllers employ an easy-to-read, 14-segment large color LCD display, along with navigation keys, thus greatly increasing the monitoring and operating capabilities. A ladder sequence function is included as standard. The short depth of the controller helps save instrument panel space. The UT35A/UT32A also support open networks such as Ethernet communication.

    Vidieť viac

Hore