For SMARTDAC+ GX/GP/GM series, the values on the numeric display of unwired channels fluctuate. What causes this?

That kind of thing can happen If you set the input range on an unwired channel to TC or DC voltage (1 V or less, when open between input terminals). Set the range of unwired channels to “Skip," or short between terminals.

Súvisiace produkty a riešenia

  • Modular GM10

    SMARTDAC+TM GM10 data logger has a modular architecture that can acquire necessary data. By supporting not only I/O but also many communication protocols such as 920MHz wireless, Modbus and so on. Monitor and setting changes are available through Bluetooth. Supporting FDA 21 CFR Part11 and AMS2750E/NADCAP.

    Vidieť viac
  • Touch Screen GP10/GP20

    The SMARTDAC+TM GP10/GP20 is a portable paperless recorder with a modular architecture on the back panel and has a data logging function to acquire the required data. By supporting not only I/O but also many communication protocols, you can connect to various devices. GP utilizes AI. Supporting FDA 21 CFR Part11 and AMS2750E/NADCAP.

    Vidieť viac
  • Touch Screen Paperless Recorder GX10/GX20

    The SMARTDAC+TM GX10/GX20 is a panel mount paperless recorder with a modular architecture on the back panel and has a data logging function to acquire the required data. By supporting not only I/O but also many communication protocols, you can connect to various devices. GX utilizes AI. Supporting FDA 21 CFR Part11 and AMS2750E/NADCAP.