I'm doing integral flow calculations on the DX1000/DX2000. I want to reset the integral flow every hour and every day, but how should I configure that?

(1) As an example, enter the following formulas for calculating flow on MATH channel 1 and MATH channel 2.
101=TLOG.SUM(001)
102=TLOG.SUM(001)

(2) MATH channel 1 resets hourly, and MATH channel 2 resets daily.
To set the reset timing, select MENU key > [to Setting mode] > Setting menu tab > MATH channel > TLOG rolling average, turn reset of each MATH channel ON/OFF, and specify a reset timing.

Set the reset timing separately under "Timer" or "Match time timer".