Temperature Monitoring module
The module, occupying a single slot, monitors four channels of temperature inputs.
As input conditions and other data that are needed for temperature monitoring are stored in the module, no parameter setup is required at system startup.
Details
Features
- High accuracy, high resolution, high speed
The input sampling period may be selected from 10ms, 100ms, or 200ms. The input conversion accuracy is ±0.1% of full scale, and the input resolution is 0.1℃ (using 5-digit representation). Low-resolution operation (using 4-digit representation) is also available. - Universal input
The input type may be set to thermocouple, RTD, or DC voltage for each channel. - ToolBox for Temperature Monitoring Modules
A dedicated ToolBox software is provided for this module. With this software, you can easily set up various parameters of the module and monitoring by following screen instructions.
Specifications
General Specifications
Item | Specification | ||
---|---|---|---|
F3CX04-0H | |||
Number of Channels | 4 channels | ||
Isolation | Between input terminals and internal circuit | Isolated (photocouplers, and capacitive / inductive coupling devices) (tested for 1500 V AC voltage withstanding for 1 minute) |
|
Between input terminals | |||
Alarm types | 4 types of alarm: input upper limit alarm, input lower limit alarm (with or without waiting for each of the above 2 alarms) |
||
Number of alarm outputs (input relays) | 4 points per channel (Only alarms 1 and 2 have input relays) | ||
Alarm delay timer | Yes | ||
Warm-up time | 30 minutes min. | ||
Max. allowable ambient temperature change rate*1 | 10 ℃ /h max. | ||
Mounting position | Horizontal or inverted orientation not allowed | ||
External connection | 40-pin spring terminal block*2 | ||
External dimensions*3 | 28.9(W)×100(H)×104.2(D)mm | ||
Current consumption | 200 mA at 5 V DC | ||
Weight | 160 g | ||
Surrounding air temperature range | Operating : 0 to 55 ℃ | ||
Storage : -20 to 75 ℃ | |||
Surrounding humidity range | Operating : 10 to 90% RH (non-condensing) | ||
Storage : 10 to 90% RH (non-condensing) | |||
Surrounding atmosphere | Must be free of corrosive gases, flammable gases or heavy dust. |
*1 : The stated accuracy for the reference junction for thermocouple input deteriorates if the ambient temperature change exceeds this rate.
*2 : When wiring to this module, be sure to use the terminal block provided. The 40-pin spring terminal block (Part No.: T9113PL) for this module can be purchased separately as a spare part.
*3 : External dimensions excluding protrusions (for details, see the External Dimensions drawing).
Input Specifications
Item | Specification | |
---|---|---|
Input sampling period*1 | 10 ms, 100 ms, 200ms | |
Input types and ranges | Universal input Individual inputs separately configurable by software or collectively by hardware Thermocouple input : 15 ranges RTD input : 9 ranges DC voltage input : 6 ranges |
|
Burnout detection | Thermocouples or RTDs are checked for burnout. Up-scale, down-scale, or none may be selected. |
|
Detection current |
Thermocouple | 100 nA max. |
RTD | 100 nA max. | |
Input insulation resistance | 1 MΩ min. | |
Allowable signal source resistance |
Thermocouple or DC mV input |
250 Ω max. |
DC voltage input | 2 kΩ max. | |
Allowable wiring resistance | RTD | 10 Ω max per wire (three wires must have the same resistance) |
Measuring current | RTD | Approx. 250 μA |
Reference junction compensation | Thermocouple*2 | ± 2.0 ℃ (0 to 55 ℃) |
Allowable input voltage range | -20 to 20 V DC | |
Noise reduction*3*4*5 | Common mode | 120 dB (50 / 60Hz)min. |
Normal mode | 40 dB (50 / 60Hz)min. | |
Effect of ambient temperature |
± 0.01% / ℃ or ± 1μV / ℃, whichever is greater |
*1 : You can select an input sampling period of 10 ms for 4 channels, 100 ms for 2 channels, 100 ms for 4 channels, or 200 ms for 4 channels.
*2 : This value assumes that all input terminals are correctly wired (that is, using ferrule, wire diameters and connections are correct).
*3 : This value assumes that the power supply frequency is correctly selected.
*4 : This module continues to operate at a input accuracy of ±0.5% max. of F.S. during the radiated electromagnetic field test.
*5 : This is the value when an input sampling period of 100ms or 200ms is selected. If 10ms is selected, 50/60 Hz noise canceling is not be enabled.
Downloads
Specificații Generale
Cauți mai multe informații despre oamenii noștri, tehnologie și soluții?
Contactează-ne