Field Wireless Multi-Function Module FN510 with “Field Wireless Communication Module FN120” is connectable with a field wireless network as a field wireless device. This product acquires sensor data from a connected sensor and transmits it to a field wireless network through FN120. Refer to General Specifications of FN120 for an overview and detailed information.
Features
Various Input / Output functions :
Analog input, digital input/output or pulse input are selectable(Measurement code: A).
ACAI function; from the AC voltage to dedicated accelerometer input, acceleration or velocity can be measured (Measurement code: C).
Connect various sensor to the field wireless network :
This product transmits sensor value acquired from a 4-20 mA analog device (Measurement code: A) or a dedicated accelerometer (Measurement code: C) to the host system via field wireless network.
Installation flexibility :
Cable elimination allows installing a device at locations where it was previously either inaccessible or cost-prohibitive because of cable management and cost.
Small and lightweight housing with LCD :
This product has a small and lightweight housing with a built-in LCD that displays the process data and communication status.
Details
Specifications
Power Supply Specifications |
Battery | Dedicated battery pack Rated voltage: 7.2 V Rated capacity: 19 Ah Battery Pack:2x primary lithium-thionyl chloride batteries With battery case (batteries sold separately) |
---|---|---|
Performance Specifications |
Update Period | [Measurement code: A] 1 to 3600 s selectable* *: When using the digital output, more than 2 s is accepted. [Measurement code: C] 10 to 3600 s selectable |
Battery Characteristics |
[Measurement code: A] Typical battery life when using analog input or digital input is 10 years * 1 or 7 years * 2 and when using digital output with always on is 3 years * 3 or 2 years * 1 in the following conditions. * 4 - Ambient temperature: 23 ±2°C - Device role: IO mode - LCD display: off *1: Update period: 10 s *2: Update period: 5 s *3: Update period : 30 s *4: Environmental condition such as vibration and the type of connected device may affect the battery life. [Measurement code: C] Typical battery life when using piezoelectric accelerometer is 10 years * 5 or 2 years * 6 in the following conditions. * 7 - Ambient temperature: 23 ±2°C - Device role: IO mode - LCD display: off - Sampling frequency: 20 kHz - Sampling points: 1024 points *5: Update period: 60 s *6: Update period: 10s *7: Environmental condition such as vibration and the type of connected device may affect the battery life. |
|
Functional Specifications |
Input | [Measurement code: A] See Table 1. [Measurement code: C] See Table 2. |
Output | Communication specifications between this product and FN120 are below. Communication Mode: Half-duplex communication (RS485 compliant) Communication Speed: 9600 bps Connector: 5-pin round connector dedicated Cable: Max 20 m (dedicated cable) |
|
Power Supply | Power supply to the FN120 Supply voltage: 3.5 V Supply current: 50 mA Power supply to sensors [Measurement code: A] None [Measurement code: C] See Table 2 |
|
Installation Environment |
Ambient Temperature Limits | Operating: -40 to 85 °C (attitude up to 3000 m), -30 to 80 °C (LCD visible range) Storage: –40 to 85 °C |
Ambient Humidity Limits | Operating: 0 to 100%RH (non-condensation) Storage: 0 to 100%RH (non-condensation) |
|
Ambient Temperature Gradient | Operating: ±10°C/h or less Storage: ±20°C/h or less |
|
Vibration Resistance | 0.21 mm P-P (10 - 60 Hz), 3G (60 - 2 kHz) | |
Shock Resistance | 50 G 11 ms | |
Regulatory Compliance Statements |
CE Conformity | EMC: EN61326-1 Class A Table 2, EN55011 Class A Safety: EN61010-1 (Indoor/Outdoor use) |
Canadian Safety Standards | CAN/CSA-C22.2 No.61010-1 CAN/CSA-C22.2 No.94.1, CAN/CSA-C22.2 No.94.2 IEC 60529 |
|
Degrees of Protection | IP66, IP67 and Type 4X apply when the connector is properly tightened. | |
Explosion Protected Types |
FM (United States or Canada), ATEX, IECEx Intrinsically safe Approval | |
Physical Specifications | Connections | Refer to “MODEL AND SUFFIX CODES” |
Housing Material | Plastic (Polycarbonate) | |
Weight | 500 g (without mounting bracket, clamp, and battery) |
[Measurement Code: A]
Table 1. Input / Output for Measurement code A
Function | Item | Specifications |
---|---|---|
4-20 mA Analog Input (AI)* 1 | Number of input channels | 1 |
Input signal | 4 to 20 mA DC | |
Range | 0 to 25 mA | |
Internal shunt resistor | 10 Ω | |
Accuracy | ±16 uA | |
Temperature coefficient | ±3.2 uA/10°C | |
Digital Input (DI) *1*2 | Number of input channels | 2 |
Input signal | Dry contact input | |
Maximum on resistance | 200 Ω | |
Minimum off resistance | 50 kΩ | |
Current value when contact is on | IN1:0.2 mA IN2:1 mA |
|
Digital Output(DO) *1*3 | Number of output channels | 1 |
Output signal | Dry contact output | |
Maximum load current | 125 mA DC | |
Maximum load voltage | 30 V DC | |
Pulse Input (PULSE) *1*2 | Number of input channels | 1 |
Input signal | Dry contact input | |
Maximum on resistance | 200 Ω | |
Minimum off resistance | 50 kΩ | |
Minimum detection time *4 | 5 ms | |
Maximum input frequency | 100 Hz | |
Counter range | 0 to 999999 |
*1: The input channels are non-isolated and share one common ground.
*2: Do not apply a voltage to a DI or PULSE from the outside.
*3: The digital output terminal is configured as open-drain. The voltage and current applied to a digital output terminal should be within the specified range.
*4: Minimum time required to detect an contact becomes off.
[Measurement Code: C]
Table 2. Input for Measurement code C
Function | Item | Specifications |
---|---|---|
AC Analog Input (AI) | Number of input channels | 1 |
Input signal | 0.1 to 3.2 V | |
Sensing mode*1 | Acceleration, Velocity, Velocity LPF160 Hz (Gain High, Gain Low) |
|
Measurement data | Peak, RMS, Peak/RMS | |
Sampling Frequency | 1, 2, 5, 10, 20 kHz | |
Sampling Points | 1024, 2048, 4096 points | |
Frequency range | 10 Hz to 10000 Hz | |
Range *2*3 | Acceleration: 0 to 300 m/s2 Velocity:0 to 160 mm/s |
|
Accuracy (100 Hz) *4*5 | Acceleration: ±(2% of reading + 2 m/s2) Velocity: ± (10% of reading +1 mm/s) |
|
Sensor power supply voltage | 3.4 V typ. | |
Sensor power supply current | 10 mA max. |
*1: Acceleration mode is used to measure the relatively high frequency vibration. Velocity mode is used to measure the relatively low frequency vibration. Velocity LPF 160 Hz mode is used to measure the near 160 Hz.
*2: Range is due to combination of LN01 Piezoelectric Accelerometer.
*3: The relationship of the measurable frequency and the measurable range due to combination of LN01 Piezoelectric Accelerometer, see Figure1 and 2.
*4: This is an accuracy of only FN510. (Ambient temperature -40 to 85ºC, the entire measurement range).
*5: Measurement accuracy due to combination of LN01 Piezoelectric Accelerometer, see Table 3.
Table 3: Measurement accuracy with combination of LN01 Piezoelectric Accelerometer (reference value)
Conditions | Accuracy (100 Hz) |
---|---|
Ambient temperature -40 to 85ºC, the entire measurement range | Acceleration: -27 to +17% of reading ± 2 m/s* 2 rms Velocity: -35 to +25% of reading ± 1 mm/s rms |
Ambient temperature 25±10ºC, the entire measurement range | Acceleration: ± (15% of reading + 0.8 m/s* 2 rms) Velocity: ± (23% of reading + 0.2 mm/s rms) |
Zasoby
Hydro power
Downloads
Broszury
- Wireless vibration sensor FN510 (ACAI type) (809 KB)
- Field Wireless Product Profile (479 KB)
- Yokogawa Field Wireless Solution (3.4 MB)
Instrukcje obsługi
- Field Wireless Multi-Function Module (4.6 MB)
- Field Wireless Multi-Function Module (Accelerometer Input) (3.9 MB)
- LN01 Piezoelectric Accelerometer (for FN series) (1.1 MB)
- China RoHS for Accessories (Battery pack assembly, Battery case, Batteries) (158 KB)
- China RoHS for Accessories (Antenna, Remote antenna cable) (178 KB)
Ogólne specyfikacje
Oprogramowanie
- Field Wireless Device Restart Tool
- Field Wireless Device Restart Tool (Instruction Manual) (1.3 MB)
- FN510 Device Description (DD) and Capabilities File (CF) for Analog, Digital and Pulse Input and Digital Output (56 KB)
- FN510 Device Description (DD) and Capabilities File (CF) for Accelerometer Input (88 KB)
- FN510 Device Description (DD) and Capabilities File (CF) for Analog, Digital and Pulse Input and Digital Output for 3rd party GW (56 KB)
- FN510 Device Description (DD) and Capabilities File (CF) for Accelerometer Input for 3rd party GW (88 KB)
Certyfikaty
- WCI certification for FN510 (433 KB)
Schematy
Wideo
Szukasz dodatkowych informacji na temat naszych pracowników, technologii i rozwiązań?
Kontakt