I set "Alarm Sound = ON" in the SMARTDAC+ GM's Web application, but the alarm won't sound. Why?

The alarm is only enabled when you set Display = Hold in the Alarm basic settings. For details, see section 3.1.3, “Changing the Display Settings on the Browser” in user's manual IM 04L55B01-01EN.

Powiązane produkty i rozwiązania

  • Modular GM10

    SMARTDAC+TM GM10 data logger has a modular architecture that can acquire necessary data. By supporting not only I/O but also many communication protocols such as 920MHz wireless, Modbus and so on. Monitor and setting changes are available through Bluetooth. Supporting FDA 21 CFR Part11 and AMS2750E/NADCAP.