I want to connect the GX60 expansion unit to the SMARTDAC+ GM10 but error E4 appears on the expansion module. What should I do?

There is a duplicate unit number. Use the dip switches of the expansion modules connected to each unit to ensure that the unit numbers do not overlap.

For information on setting dip switches, see “Setting Up the GX90EX Expansion Module" in the First Step Guide included in the packaging.

Related Products & Solutions

  • Modular GM10

    SMARTDAC+TM GM10 data logger has a modular architecture that can acquire necessary data. By supporting not only I/O but also many communication protocols such as 920MHz wireless, Modbus and so on. Monitor and setting changes are available through Bluetooth. Supporting FDA 21 CFR Part11 and AMS2750E/NADCAP.