There's no output with an RTD temperature converter. What should I do?

  1. Check the power supply wiring.
  2. Check whether the power supply voltage meets the specifications.
  3. For Pt100 input specifications, connect a 100 Ω resistance between input terminals A and B, short the B terminals, then confirm that the output is equivalent to 0°C.
  4. If the output signals is of the current specifications, attach an external 250 Ω resistance and measure the voltage.

Related Products & Solutions

  • JUXTA F Series Signal Conditioners

    F Series signal conditioners are compact, space-saving (24 mm width) signal conditioners with front panel terminals. The microprocessor based models provide field configuration capability and minimum stock of spares. The installation is either DIN-Rail, Rack or Wall mounting, and the power supply is 24 V DC.

    See More
  • JUXTA W Series Signal Conditioners

    Compact size, versatile mounting, and microprocessor based high performance capabilities makes the W Series an excellent choice for almost every application. The specifications of W Series signal conditioners are as same as F Series signal conditioners except for power supply voltage, second output and case width.