There's no output with a thermocouple temperature converter. What should I do?

  1. Check the power supply wiring.
  2. Check whether the power supply voltage meets the specifications.
  3. Confirm that the accessory RJC sensor is connected to the input terminal.
  4. Short the input terminals, then confirm that the output is equivalent to the terminal temperature.
  5. If the output signals is of the current specifications, attach an external 250 Ω resistance and measure the voltage.

Related Products & Solutions

  • JUXTA F Series Signal Conditioners

    F Series signal conditioners are compact, space-saving (24 mm width) signal conditioners with front panel terminals. The microprocessor based models provide field configuration capability and minimum stock of spares. The installation is either DIN-Rail, Rack or Wall mounting, and the power supply is 24 V DC.

    See More
  • JUXTA W Series Signal Conditioners

    Compact size, versatile mounting, and microprocessor based high performance capabilities makes the W Series an excellent choice for almost every application. The specifications of W Series signal conditioners are as same as F Series signal conditioners except for power supply voltage, second output and case width.