With the Ethernet gateway function for VJET and UT351/UT551, the serial communication timeout with devices connected downstream is about 4-5 seconds, therefore you should set the timeout time on GateCONTROL at about 5 seconds or perhaps more.
Related Products & Solutions
-
WX1 Gate Interface Software
Model : WX1