AR2-PL
Notice: This product was discontinued on Sep 30, 2015.

Resources

There is no load current rating. With this model no load current flows because it is connected in parallel to the load.
The “AR-PS” is available. Note that this is not JIS-compliant.
Yes, you need it regardless of the presence or absence of voltage. We recommend the AR-LP.
The insulation resistance value at the surge arrester terminal block between the I/O terminals and ground is 100 MΩ or more/500 VDC. The withstand voltage between I/O terminals and ground is 1000 VAC/1 minute (or 1500/1 minute for the AR-PH onl...
Yes. It's the E9731TW. (Please consult with your dealer at the time of purchase.)
Yes. The adapter for mounting on a DIN rail is an option.
They are voltage limiting lightning arresters.
For converters with an open detection function, during open detection the line-to-line is 40 V, therefore we recommend using the AR-HA (max. continuous line-to-line voltage of 70 V) .
Yes, that is not a problem.
Yes, the AR-SA.
Yes, the AR-LP. It has a rated (load) current of 2 A. Note that this does not support JIS.
Can I mount on DIN rails?
(ns-faq-ar-16004-select)
A DIN rail adapter can be included with an option when purchasing the surge arrester. If you need to purchase an adapter later, select the AR8-01_DIN rail adapter. ...
Can I use the AR-RT for the Pt50 Ω RTD?
(ns-faq-ar-16005-select)
Yes.
You can use the AR-LP. Note that this is not JIS-compliant.
It uses a zinc oxide varistor.
Yes, the AR-LP (for 2-wire pulse signals, 50 VDC or less)

Looking for more information on our people, technology and solutions?

Contact Us

Top