The PK200 current-to-pneumatic (I/P) converter offers a low-cost method to convert a milliamp input (4-20 or 10-50mA analog signals) to a proportional pneumatic (air pressure) output. The unit is designed for a broad range of process control applications, including those that feature pneumatic actuating equipment. The PK200 features built-in stainless steel input/output gauges. The reliable PK200 performs electronic feedback control while maintaining accuracy of ±0.5 percent of span and linearity of ±0.2 percent of span. Built with energy savings in mind, the PK200 consumes only 4 normal liters/minute (4 NL/min) air while providing output air capacity of 110 NL/min. PK200 complements Yokogawa's existing line of Quality Solutions for its North American customers: pressure and temperature transmitters, flowmeters, on-line analyzers, recorders, digital loop controllers and an entire family of distributed control systems.
Detalles
Features
-Highly accurate signal conversion with minimum effects from process environments
Stainless steel bracket, epoxy coating, and other optional specifications allow the PK200 to be used in a variety of applications.
-Highly reliable, accurate electronic feedback
-Energy-saving design for improved economy
Max. air consumption: 4 Nl/min when air supply pressure is 140 kPa
Max. output air capacity: 110 Nl/min when air supply pressure is 140 kPa
-Excellent operability by access to only one side of the product
Specifications
Linearity | ±0.2% of span |
---|---|
Hysteresis | 0.2% of span |
Repeatability | 0.1% of span |
Input Signal | 4 to 20mA DC /10 to 50mA DC |
Air Supply Pressure | 140kPa (Standard Output) 240kPa (Doubled output) |
Air Consumption | Max. 4 Nl/min. or 0.24 Nm3 /hr at 140 kPa (20 psi) air supply pressure. |
Output Air Capacity | Max. 110 Nl/min. or 6.6 Nm3 /hr at 140 kPa (20 psi) air supply pressure. |
Output Signal | 20 to 100kPa (Standard Output) 40 to 200kPa (Doubled output) |
Operating Temperature Limits | -40 to 80 deg C (-40 to 176 deg F) (General use) |
Supply Air, Output Signal, Output Gauge Connections | Rc1/4 or 1/4 NPT female |
Electrical Connection | G1/2, G3/4, 1/2 NPT or 3/4 NPT female |
Mounting | Surface or 2-inch pipe. |
Approximate Weight | 2.8kg |