Are there any restrictions on which slots input/output modules for SMARTDAC+ GX/GP series are installed into?

If using the product's reference junction compensation function with GX90XA module thermocouple inputs, do not install a "GX90XA-10-C1" mA module or "GX90WD" digital input module into the slot to the right* of the GX90XA module (the side with the smaller slot number). If you install those modules there, RJC accuracy cannot be guaranteed.
*When looking from the back panel of the GX/GP main unit or the front panel of an expansion unit.

Productos y Soluciones Relacionadas

  • Touch Screen GP10/GP20

    • SMARTDAC+TM GP10/GP20 Yokogawa Data Logger
    • Paperless recorder
    • Intuitive, human-centric design
    • Web-enabled functionality
    • Scalable architecture
    Leer Más
  • Touch Screen GX10/GX20

    • SMARTDAC+ Touch Screen GX10/GX20
    • Multi-point touch screen recorder
    • Intuitive design
    • Web functionality
    • Scalable
    • GX20 supports 920 MHz band wireless 
    Leer Más

Top