Base module
e-RT3 는 5, 9, 13 및 16 슬롯의 4가지 유형의 기본 모듈을 제공합니다.
Power Supply module
각 기본 모듈에 대해 하나의 전원 공급 장치 모듈을 설치합니다.
Details
Lineup
Name | Type name | Specifications |
---|---|---|
Base module*1 | F3BU05-0D | For power supply(F3PU20/F3PU30/F3PU26/F3PU36)+ 5 slots(CPU+I/O) |
F3BU09-0N | For power supply(F3PU20/F3PU30/F3PU26/F3PU36)+ 9 slots(CPU+I/O) | |
F3BU13-0N | For power supply(F3PU20/F3PU30/F3PU26/F3PU36)+ 13 slots(CPU+I/O) | |
F3BU16-0N*2 | For power supply(F3PU20/F3PU30/F3PU26/F3PU36)+ 16 slots(CPU+I/O) |
*1:The rail mount kit must be purchased separately.
*2:This unit cannot be used with the rail mount kit.
Specifications
F3BU05-0D | F3BU09-0N | F3BU13-0N | F3BU16-0N | |
---|---|---|---|---|
Number of slots | 5 | 9 | 13 | 16 |
Number of I/O slots*1 | 4 | 8 | 12 | 15 |
Current consumption | 50mA (5V DC) | |||
Weight (g) | 210g | 340g | 470g | 550g |
*1 : Number of I/O slots that can be used with a single CPU module
Lineup
Name | Type name | Specifications |
---|---|---|
Power supply module | F3PU20-0S | 100 to 240V AC,5V DC/4.3A rated output (for 5, 9, 13, and 16 slots, M4 screws) |
F3PU30-0S | 100 to 240V AC,5V DC/6.0A rated output (for 5, 9, 13, and 16 slots, M4 screws) | |
F3PU26-0S | 24V DC,5V DC/4.3A rated output (for 5, 9, 13, and 16 slots, M4 screws) | |
F3PU36-0S | 24V DC,5V DC/6.0A rated output (for 5, 9, 13, and 16 slots, M4 screws) |
Specifications
F3PU20-0S | F3PU30-0S | F3PU26-0S | F3PU36-0S | |||
---|---|---|---|---|---|---|
Supply voltage | 100-240 V AC, single phase, 50/60 Hz | 24V DC | ||||
Supply voltage fluctuation range | 85 to 264 V AC, 50/60Hz ±3Hz | 15.6 to 31.2 V DC | ||||
Power consumption | 85 VA | 100 VA | 33.1 W | 46.2 W | ||
Inrush current | 20 A max. (120 V AC, Ta=25℃) 45 A max. (240 V AC, Ta=25℃) |
20 A max.(31.2 V DC, Ta=25℃) | ||||
Rated output voltage | 5 VDC | |||||
Rated output current | 4.3 A | 6.0 A | 4.3 A | 6.0 A | ||
Insulation resistance | 500 V DC 5M Ω or more between external AC terminals and FG terminal | 500 V DC 5M Ω or more between external DC terminals and FG terminal | ||||
Dielectric strength | 1500 V AC for 1 minute between external AC terminals and FG terminal | 1500 V AC for 1 minute between external DC terminals and FG terminal | ||||
Allowable momentary power failure time | 20ms | |||||
Noise immunity | Noise level:1500 Vp-p when measured by a noise simulator having a 1 μs of noise pulse width, 1ns of rise time, and 25 Hz to 60 Hz of repetition frequency | |||||
External dimensions | 58(W)×100(H)×83.2(D)mm | 58(W)×100(H)×126.1(D)mm | 58(W)×100(H)×83.2(D)mm | 58(W)×100(H)×126.1(D)mm | ||
Weight | 320g | 380g | 320g | 410g |
Downloads
General Specifications
- FA-M3/ e-RT3 Overview (1.1 MB)
- Basic Modules (Base, Power Supply CPU Modules and ROM Packs) (2.0 MB)
- Standard compliant products (192 KB)
기술 및 솔루션, 요꼬가와에 대한 자세한 정보를 찾고 계십니까?
견적 및 기술문의