MORITA Mikihiko *1 KAKIHARA Kaname *1 HATTORI Hitoshi *1 TAKAHASHI Masahiko *1

We have added a fieldbus interface to the DAQSTATION. In order to take advantage of the multi-channel measurement and trend-display capabilities of the DAQSTATION, we installed multiple analog input (MAI) and multiple analog output (MAO) function blocks. The DAQSTATION thus has become able to deal with a wide range of applications, from large-scale instrumentation using distributed control systems (DCS) to stand-alone small-scale supervisory systems. The DAQSTATION is now capable of easy networking through connection between a fieldbus and Ethernet. This paper describes examples of such applications.

  1. Network Solutions Div.

INTRODUCTION

Figure-1-DX-Series-of-DAQSTATION
Figure 1 DX Series of DAQSTATION

Yokogawa's industrial recorders have been widely used in order to monitor and record data acquired from the field. Concurrently, sensors in the field have been made increasingly intelligent and come to hold not just "data" but "information" of additional value provided by such functions as failure detection and statistical analysis. As a result, recorders are required to serve as media for processing such information and convey it in an easy-to-understand form.

The DX series of DAQSTATION2 released by Yokogawa in 1999 is a type of paperless recorder, a product extensively characterized as a data acquisition station. In order to extend the network capabilities of the DAQSTATION, we remodeled the DX series to support FOUNDATION™3 Fieldbus H1. In August 2000, the DX series became the world's first FOUNDATION™ fieldbus-enabled recorder to be registered with the Fieldbus Foundation in the US. The features of the DX series are described below, and its external view is given in Figure 1.

  1. A maximum of 12 analog channels for the DX100 recorder and 30 for the DX200 recorder
  2. Ethernet as a standard feature for such purposes as FTP-based data transfer, WWW monitoring and E-mail alarm transmission
  3. Storage of data in large-capacity media (memory card, Zip disk, etc.)
  4. A variety of views provided by the wide view angle TFT liquid crystal display
  5. A maximum of 24 alarm contact outputs
  6. Dustand drip-proof in compliance with IEC529-IP65 standard
  7. Support for communication based on MODBUS and FOUNDATION™ fieldbus standards

OBJECTIVES OF PRODUCT DEVELOPMENT

The following product development guidelines were adopted in order to add FOUNDATION™ fieldbus communication capabilities to the DAQSTATION.

  1. Propose specific examples of application to users, as the recorder will be the world's first fieldbus-enabled model.
  2. Make the utmost use of in-house resources already developed for Yokogawa's family of field instruments.
  3. Ensure interoperability with earlier and later systems and field instruments on the fieldbus.

FIELDBUS SPECIFICATIONS

Table 1 summarizes the fieldbus specifications of the DAQSTATION.

Table 1 Fieldbus Specifications

Item Specifications
Function block AI (8 blocks) Sends the measured/computed data of the main unit to other devices (one channel for each block).
MAI (1 block) Sends the measured/computed data of the main unit to other devices (eight channels).
MAO (1 block) Receives measured data, for example, from other devices (eight channels) to record/show them in/on the main unit.
Link master function Provided Controls communication on the fieldbus according to a preset schedule.
Interface Compliant to the FOUNDATION™ Fieldbus H1 specifications; communication speed = 31.25 kbps
Type of physical layer 113 (standard-power signaling, bus-powered, non I.S.)
Communication line requirements Power supply through communication lines.
Supply voltage: 9 to 32 V DC
Supply current: 16.5 mA max.
Signal isolation Isolation of signals on both the field and system sides. Withstanding voltage: 500 Vrms (50/60 Hz, 1 min)

The standard analog input (AI), multiple analog input (MAI) and multiple analog output (MAO) function blocks prescribed by the FOUNDATION™ fieldbus standard have been installed in the DAQSTATION. As a result, the station can exchange such data as process values with other devices on the fieldbus. The station can also control communication on the fieldbus using the Link Master (LM) function.

A fieldbus tool for the DAQSTATION, PC software for building a fieldbus system using the DAQSTATION as a communication host station, has been made available separately in anticipation of small-scale monitoring applications requiring no large-scale control system, such as a distributed control system (DCS).

HARDWARE CONFIGURATION

Architecture

Figure 2 shows the circuit diagram of the DX series.

 Figure-2-Block-Diagram-of-Circuit-Configuration
Figure 2 Block Diagram of Circuit Configuration

The fieldbus communication functions of the DAQSTATION are installed in a subsystem that is built into the main unit only when the recorder is a fieldbus model. This strategy has made it possible to configure almost all of the functions only on the subsystem side. Consequently, we were able to utilize the in-house resourcesthat were previously developed for our family of field instruments.

Functions other than the fieldbus communication functions are implemented on the main system side. Thus, the subsystem and main system are configured so that they exchange required data via internal serial communication. For details on the main system, we would like the readers to refer to reference1 recited herein.

Fieldbus Subsystems

The circuit configuration (Figure 2) of the DAQSTATION fieldbus subsystem is basically the same as that of the FOUNDATION™ fieldbus models in the EJA series of differential transmitters. The former differs from the latter, however, mainly in that:

  1. the operating frequency has been increased in order to maximize CPU performance; and
  2. signals have been isolated between the MAU and communication controller.

Programs and static parameters are stored in a flash ROM and read out of it as necessary. The SRAM is used as main memory. In addition, nonvolatile parameters, such as communication settings, are stored in an EEPROM as necessary.

SOFTWARE FUNCTIONS

Figure-3-Block-Diagram-of-Software-Functions
Figure 3 Block Diagram of Software Functions

Figure 3 is a block diagram of software functions. Like the hardware, the software of DAQSTATION is composed of two parts—the main system serving as a recorder responsible for data acquisition and the subsystem responsible for fieldbus communication.

This software configuration enables the DAQSTATION to output the analog data of measurement/computation channels being acquired by the main system, through the AI and MAI function blocks, to a maximum of 16 other devices on the fieldbus.

In addition, a maximum of 8 items of analog data acquired by other devices on the fieldbus can be input to the station through the MAO function block. Like regular analog data inputs, these data items can be recorded or displayed through the computation channel. Alternatively, they can be transmitted to a LAN via Ethernet.

Although mapping between the measurement/computation channels of the main system and AI, MAI and MAO function blocks is defined by a table within the transducer block (TB), users can make changes to the table.

The DAQSTATION is provided with the LM function and, therefore, can also be used as a link active scheduler (LAS) for controlling fieldbus communication.

APPLICATION EXAMPLES

From the standpoint of users and applications, the following three types of application are proposed for fieldbus communication based on the DAQSTATION.

Using as a Converter for Signals from Existing Sensors

Figure-4-Application-as-a-Converter-for-Signals
Figure 4 Application as a Converter
for Signals from Existing Sensors

Under an operating environment based on a host system, such as a DCS, the DAQSTATION can be used as a converter for signals coming from existing non-fieldbus-standard sensors. Figure 4 shows a schematic example of this application.

In the US and European countries, revamped plants (renovated or expanded versions of existing plants) are seen more often than newly built plants. In that case, wiring from existing sensors, including thermocouples, is often attached to such indicating instruments as recorders installed in a central operation room. When building a fieldbus instrumentation system that reuses these facilities, users can use the DAQSTATION as a converter for signals from existing sensors to the fieldbus. Thus, users can work with the station on the host system in an integral manner, while using the station as an indicating instrument as they used to. In this application, the AI and MAI function blocks of the DAQSTATION are used.

Using as a Field Indicator

Under an operating environment based on a host system, such as a DCS, the entire range of information is transferred from the field to the operator console of the host system for utilization as the results of fieldbus instrumentation. In contrast, in conventional instrumentation on-site staff members working outside a central operation room where such an operator console is installed has also been provided with such information by means of annunciators and recorders housed in cabinets.

Now that the MAO function block has been installed in the DAQSTATION in this new development, the station can be used as a "field indicator" for monitoring process values and other pieces of information in fieldbus instrumentation under the host system based operating environment. Figure 5 shows a schematic example of this application.

Using as a Supervisory Unit for Small-scale Instrumentation

Figure-5-Application-as-a-Field-Indicator Figure-6-Application-as-a-Supervisory-Unit 
Figure 5 Application as a Field Indicator Figure 6 Application as a Supervisory
Unit for Small-scale Instrumentation

The FOUNDATION™ fieldbus standard also gives consideration to the autonomous, distributed control of field instruments. Consequently, the fieldbus can be used with field instruments alone, without having to use such large-scale control systems as DCSs. This feature can be taken advantage of by using the DAQSTATION as a supervisory unit. As a result, it is possible to configure a small-scale instrumentation system, e.g., a built-in controller or an environment monitoring system, as a fieldbus system, without using any large-scale control system. Figure 6 shows a schematic example of this application. In this example, the MAO function block is used to monitor and record process values in the field, while the LM function is used to control communication on the fieldbus.

The DAQSTATION comes standard with an Ethernet port, enabling users to easily acquire trend graphs or data by having access from PCs in their offices.

INTEROPERABILITY

The DAQSTATION was submitted to the interoperability test of the Fieldbus Foundation before it was released in the market. The station has successfully passed the latest version of the test, Interoperability Test Kit (ITK) 4.0. We have verified interoperability not only with our own host system, the CENTUM, but also with some host systems from other companies.

CONCLUSION

Figure-7-External-Views-of-MobileCorder-MV-Series 
Figure 7 External Views of MobileCorder
MV Series of Data Loggers

In this article, we have discussed the compliance of the DX series of DAQSTATION with the fieldbus standard. At this point, we report that we have also remodeled the MV series of MobileCorder data loggers (Figure 7), laboratory-use sister products of the above-mentioned series, in order to support FOUNDATION™ Fieldbus H1. The fieldbus-enabled models in the MV series have already been registered with the Fieldbus Foundation.

 

 


 

REFERENCES

  1. Takahashi Masahiko, Katsuoka Shuji, Hosaka Yuuji, Kakihara Kaname, "DAQSTATION DX100/200 Series of Paperless Recorders," Yokogawa Technical Report, No. 30, 2000, p. 15-18
  2. Koyama Etsutaro, Nikkuni Masaaki, Odohira Tetsu, "EJA Series Differential Pressure Transmitter with Fieldbus Communication," Yokogawa Technical Report, No. 27, 1999, p. 9-12
  • DAQSTATION and MobileCorder are a registered trademark and a trademark of Yokogawa Electric Corporation.
  • FOUNDATION™ is a registered trademark of the Fieldbus Foundation in the US. Other trade names and designations that are referred to in this document are either trademarks or registered trademarks of the respective companies.

업종

  • 전력

    1970년대 중반, Yokogawa는 EBS 전기 제어 시스템 (EBS Electric Control System)의 출시와 함께 전력 사업에 진출했습니다. 그 이후로 Yokogawa는 전 세계 고객에게 최상의 서비스와 솔루션을 제공하기 위한 기술과 역량의 개발을 꾸준히 지속해 왔습니다.

    Yokogawa는 역동적인 글로벌 전력 시장에서 더욱 적극적인 역할을 수행하기 위해 글로벌 전력 솔루션 네트워크를 운영했습니다. 이로 인해 Yokogawa 내에서 보다 긴밀한 팀워크가 가능해져서 글로벌 리소스와 업계 노하우를 하나로 모았습니다. Yokogawa의 전력 산업 전문가들은 각 고객에게 정교한 요구 사항에 가장 적합한 솔루션을 제공하기 위해 협력합니다.

    See More
  • 정수 및 하수 처리

    Yokogawa는 보다 효율적인 사회를 만들기 위하여 에너지 최적화 기술 개발, 온실가스 감축, 오염 물질로부터 환경을 보호하는 견고한 제품 제작 등을 통해 지속 가능한 수자원 생산을 위한 제어 솔루션을 제공하고 있습니다. Yokogawa의 첨단 기술과 폭넓은 애플리케이션 노하우를 통해 고객과 협력하여 사업을 활성화하고 플랜트 수명주기 전반에 걸쳐 높은 가치를 제공할 수 있는 지속 가능한 솔루션을 제공합니다. 당사의 기술과 제품은 플랜트의 성능을 향상시키고 오늘날의 수자원 시장에서 경쟁적으로 운영할 수 있도록 보장하며 운영비를 절감합니다. Yokogawa는 지자체 및 공업용수 처리 시장에서 광범위한 수처리 응용 분야를 지원합니다.

    See More

Related Products & Solutions


Top