Measurement of O2 Concentration in Exhaust Gases from Pulverized Coal-fired Boilers

다운로드 (707 KB)

Introduction

In a pulverized coal-fired boiler of a large power plant, an oxygen analyzer is essential for combustion control. Exhaust gases from the pulverized coal boiler contain a large quantity of dust and flow very fast. Oxygen analyzers that employ a sampling method may be subject to wear or clogging, resulting in increased maintenance workload and cost.

A solution to this problem is the ZR22G/ZR802G Zirconia Oxygen Analyzer that has no sampling system and utilizes a long-life sensor. A probe protector is attached to protection it against wear.

Expected Benefits

  • Improves combustion efficiency for pulverized coal-fired boilers 
  • Ensures stable, continuous oxygen measurement 
  • Reduces operating cost 
  • Minimizes the need for equipment replacement

Process Overview

While heavy oil, light oil , kerosene commonly used as a boiler fuel, coal is also used because it is inexpensive and readily available. Unlike oil, coal and gas produce a large quantity of ashes when it is burned, necessitating pulverized coal-fired boilers to be equipped with an ash removal system such as a cyclone. Exhaust gases from these boilers contain a large quantity of dust (10 to 30 g/Nm3) and flow very fast as the result of the large volume of air being blown into the boiler. For oxygen measurement in large ducts, a probe with a long insertion length is used.

Pulverized Boiler

Solution Details

Field Data

Process conditions

Measurement point Economizer outlet
Temperature 300 to 400°C
Flow rate ≤ 30 m/s
Pressure ±1.5 kPa
Dust approx. 15 g/Nm3 or less
Fuel pulverized coal

Measurement system

Detector ZR22G-☐☐☐-S-☐-☐-☐-☐-E-A/CV
Probe protector ZO21R-L-☐☐☐-☐*B
Converter ZR802G-☐-☐-N-N /☐
Flow setting unit ZA8F-☐*C
Pressure regulator G7013XF or G7014XF
Case for calibration gas cylinder E7044KF

Note: the calibration gas cylinder must be purchased locally

Utilities

Rated voltage 100 to 240 V AC
Rated frequency 50/60 Hz
Power consumption 330 VA (Max. 800 VA)
Instrument air 300 to 700 kPa

ZR802G

Notes

  • A probe protector should be attached to the probe for protection against wear or damage. The probe protector should be mounted with the notch of the probe head pointing downstream in the gas flow.
  • It is recommended that the detector be installed with the probe tip pointing downward. As shown in the figure, it may be installed horizontally, too. The probe head tip should not point upstream in the gas flow.

업종

  • 전력

    1970년대 중반, Yokogawa는 EBS 전기 제어 시스템 (EBS Electric Control System)의 출시와 함께 전력 사업에 진출했습니다. 그 이후로 Yokogawa는 전 세계 고객에게 최상의 서비스와 솔루션을 제공하기 위한 기술과 역량의 개발을 꾸준히 지속해 왔습니다.

    Yokogawa는 역동적인 글로벌 전력 시장에서 더욱 적극적인 역할을 수행하기 위해 글로벌 전력 솔루션 네트워크를 운영했습니다. 이로 인해 Yokogawa 내에서 보다 긴밀한 팀워크가 가능해져서 글로벌 리소스와 업계 노하우를 하나로 모았습니다. Yokogawa의 전력 산업 전문가들은 각 고객에게 정교한 요구 사항에 가장 적합한 솔루션을 제공하기 위해 협력합니다.

    See More
  • 화력발전

    석탄, 석유 또는 가스를 연료로 사용하는 화력발전은 전 세계적으로 대부분의 전력을 생산하고 있습니다.

    See More

Related Products & Solutions

  • 지르코니아식 산소/습도 분석기 ZR22G, ZR802G

    이 장비는 고온에서 산소 및 습도 측정이 가능하며 매우 정교한 지르코니아 센서가 장착된 ZR22G 검출기와 디지털 통신 및 데이터 로그 기능을 갖춘 변환기 ZR802G로 구성됩니다. ZR22G 및 ZR802G는 샘플링 장치 없이 연속적으로 측정할 수 있습니다. 센서의 성능을 자가진단하고 (교정 가스를 사용하지 않음) 현장에서 Heater assembly를 교체하여 유지 보수를 용이하게 하여 작업 비용을 줄일 수 있습니다.

     

    See More
  • Oxygen Analyzers

    산소 분석계는 연소 제어, 공정 품질, 안전 및 환경 응용 분야에서 중요한 측정을 제공합니다.

    See More

Top