Introduction
A furnace for heating slabs needs to be operated under low oxygen conditions at high temperatures of 1000℃ and above to prevent oxidation of the steel. The measurement of oxygen concentrations in the furnace is essential in this process.
The ZR22G/ZR802G Zirconia Oxygen Analyzer requires no sampling system and utilizes a long-life sensor, and is therefore ideally suited for measurement of oxygen concentrations in a hightemperature environment. The ZR22G detector with the ZO21P high temperature probe adapter can be used in gas furnaces at temperatures up to 1400℃.
Expected Benefits
- Maintains high product quality by monitoring oxygen concentrations in steel mill reheating furnaces
- Ensures stable, continuous measurement of oxygen concentrations
- Reduces operating costs
Process Overview
Slabs are loaded on a conveyor and fed to a reheating furnace, which is heated to between 900 and 1400℃ by burners that use fuels such as by-product gas. In order to keep the oxygen concentration between 1 and 2%, it is monitored in the preheat, heat , and soak zones. The slabs are heated uniformly without being oxidized, and then sent to the next processing stage.
Solution Details
Field Data
Process conditions | |
---|---|
Measurement point: | furnace reheat, heat, and soak zones |
Temperature: | 900°C to 1400°C |
Pressure: | 30 to 50 kPa |
Dust: | Trace |
Fuel: | Gas |
Measurement system
Detector: | ZR22G-015-S-Q-☐-☐-☐-E-A/CV |
---|---|
High temperature probe adapter: | ZO21P-H-☐-☐☐☐-☐*B |
Auxiliary ejector for high temperature use: | E7046E☐ |
Converter: | ZR802G-☐-☐-N-N/☐ |
Flow setting unit: | ZA8F-☐*C |
Calibration gas unit | |
Pressure regulator for gas cylinder: | G7013XF (inlet W22, outlet Rc1/4) or G7014XF (inlet W22, outlet 1/4NPT) |
Case assembly for calibration gas cylinder: | E7044KF |
Note: the calibration gas cylinder must be purchased locally.
Probe Adapter
Utilities | |
---|---|
Power supply: | 85 to 264 V AC, 50/60 Hz |
Instrument air (reference gas): | pressure, 300 to 700 kPa |
Notes
The material selected for the high temperature probe adapter depends on the temperature of the sample gas. Follow instructions carefully when installing the probe.
SUS: | Sample gas temperature ≤ 750°C |
---|---|
Probe orientation: | vertical or horizontal |
Inconel: | 750°C < sample gas temperature ≤ 900°C Probe orientation: vertical or horizontal |
SiC: | 900°C < sample gas temperature ≤ 1400°C Probe orientation: vertical |
Note:
When the probe is installed horizontally, bracings must be provided for mechanical support