Level Measurement of Open CIP Chemical Tank

Introduction

  • At food, beverage and pharmaceutical production lines, tanks and pipes are cleaned and sterilized every time when production is completed.
  • An open tank (Height: 2 to 4 m), open to atmosphere, is used as a chemical tank containing CIP cleaning solution. (CIP: “Clean-in-Place”).
  • Tank level is measured by pressure, but it is sometimes unstable to measure due to small gauge pressure from the tank with sanitary fittings.
Air Supply Measurement for Reactors - Plant image

 

Requirements

  • Pressure sensor with suitable measuring range for low pressure measurements. Among the pressure sensors with fill fluid liquid, there are limited options.
  • A pressure sensor without fill fluid can withstand steam and high water pressure with rapidly changing temperature, up to 150 deg C, during cleaning process.
  • Reliable and accurate performance under harsh process conditions with high noise levels.

 

Proposal

Precise measurement of liquid level can be expected with EJAC60E,YOKOGAWA’s Fluidless-type Sanitary Pressure Transmitter, that performs reliably and accurately from minimum 20 kPa on small open tanks.

EJAC60E Fluidless-type Sanitary Pressure Transmitter

 

Features of EJAC60E (= EJA560E + C10SA adapter)

  • Fluidless transmitter has no risk of process contamination with fill fluid.
  • The sensor has a robust diaphragm design for 25 MPa (3600 psi) burst pressure.
  • Transmitter performs steady even for small pressure range (example : 20 kPa, 2.9 psi).
  • Sensor is suitable for high temperature steam cleaning and continuous process temperature up to 150degC (302degF).

EJAC60E input-output test data

Input-output test data:
Max span of EJA560E A capsule : 400 kPa.
Set range : 0 to 20 kPa (Span 20 kPa)
Catalog spec of Accuracy for this range : 0.75 %
Three A capsule units were tested after the range was set for 0 to 20 kPa. The output signal shows much better accuracy than the catalog spec.

  • Sanitary seal multi-adapter (C10SA) for a wide range of connections is offered.
    • ISO Clamp (IDF1S, 1.5 S, 2 S, 2.5 S, 3 S, 4 S)
    • Union (ISO 38, 51, DIN 25, 40, 50)
    • Inline (DN 25, 50, 80,100), Flash (DN 40)

Sanitary seal multi-adapter (C10SA)

 

Other details of Fluidless EJAC60E

  • Resistant to excessive pressure
    • The wetted sensor part is a reinforced type SUS 329 J 14 L.
    • Metal diaphragm prevents brittle fracture
  • Resistant to condensation
    • High moisture resistance with special moisture-proof film + coating
    • Outperforms other manufacturers more than 20 times in dew condensation tests
  • Steam resistant
    • Sensor is formed by sputtering method, resulting in no aging deterioration of the joint.
    • Electrode is fused with metal to achieve the durability for 200,000 steam cycles.
Structure of the fluidless transmitter EJAC60E

Related Industries

  • 식음료

    Yokogawa는 오늘날의 식음료 기업들이 기후 변화, 소비자 수요 및 글로벌 경쟁력 향상이라는 전례 없는 도전에 직면해 있다는 것을 알고 있습니다. 이러한 도전을 극복하기 위해서는 생산, 자산 관리, 식품 안전 및 품질이라는 핵심 분야에 초점을 맞춘 혁신적인 솔루션이 필요합니다.

  • 의약품

    제약회사는 제조 데이터를 기반으로 실시간 품질 관리를 강화하여 유연하고 민첩한 생산 체계를 구축해야 합니다. Yokogawa는 고객과 협력하여 안전하고 신뢰할 수 있는 의약품 제조 솔루션을 개발하고, 디지털 혁신을 통해 규제를 준수하고 품질을 보장하며 시장 출시를 앞당겨 환자에게 더 나은 의약품을 제공합니다.

Related Products & Solutions

  • 압력 전송기

    Yokogawa 압력 전송기로 프로세스 압력을 정확하고 안정적으로 측정하면 안전하고 신뢰할 수 있으며 수익성 있는 작업을 지원할 수 있습니다.


Top