The YTA80 is a head mount type of temperature transmitter that accepts thermocouple, RTD, ohms or DC milivolts input and converts it to digital communication signal based on FOUNDATION™ Fieldbus protocol.
The YTA80 conforms to the standard DIN formB head mounting.
Common specifications:
Supply voltage, DC: Standard, YTA80/KN2: 9 – 32V
ATEX, YTA80/KS2: 9 – 30V
In FISCO installations: 9 – 17.5V
Consumption: < 11mA
Max.current increase in the event of an error: < 7mA
Isolation voltage, test: 1.5kVAC for 60sec
Isolation voltage, operation: 50VRMS/75VDC
Warm-up time: 30sec
Signal/noise ratio: min.60dB
Response time (programable): 1 – 60 sec
Updating time: < 400ms
Execution time, PID controller: <200msec
Execution time, analogue input: <50msec
Signal dynamics, input: 24 bit
Calibration temperature: 20 – 28ºC
Ambient temperature limits:
(Option code may affects limit) -40ºC to +85ºC
Vibration: IEC 60068-2-6 and IEC60068-2-64
Lloyd’s specification no.1: 4g/2 – 100Hz
Humidity: < 95%RH (non-cond.)
Tightness (enclosure / terminal): IP68/IP00
Weight: 55g