Installation cost is reduced with a multi-variable transmitter. The EJX multi-variable transmitter combines three process variables in one transmitter. It removes the need to install a separate gauge pressure transmitter, temperature transmitter and flow computer. Dedicated software for configuring the flow calculation is available (FieldMate – Flow Navigator).
Customer Issues
- Installation cost of multiple field devices is high.
- Mass flow measurement is expensive.
Utilize EJX910A/930A + Flow Navigator
- From one multi-variable transmitter, you can measure differential pressure, static pressure, temperature and mass flow. The total cost is greatly reduced.
- Flow Navigator software provides a simple, user friendly method to configure the mass flow measurement.
Utilize FieldMate
- Flow Navigator has a step by step interface based on FDT/DTM technology. You can set the data by simply selecting the primary element, and inputting the flow rate information.
- You can copy the configuration of one transmitter to another transmitter to help with multiple configurations.
EJX Multi-Variable Transmitter Outputs
① In the case of HART digital / FOUNDATION Fieldbus /Modbus, these types of outputs can transmit multi process values at the same time.
② In the case of Analog signal (4-20mA), a multiplexer can be used to convert up to three values from HART signals into 4-20mA signals. The transmitter can transmit up to four values in conjunction with the original signal.
③ In the case of ISA100(wireless), the ISA 100 adaptor can transmit up to four values from the HART signal without reconstructing an existing line.
The measurements that EJX multi-variable transmitter can transmit
Protocol |
DP | SP |
Ext. TEMP |
Other TEMP |
FLOW |
Total Flow *4 |
---|---|---|---|---|---|---|
HART *1 | ● | ● either H or L |
● | ● Capsule Amplifier Flange (/DG6) |
● | ● |
FOUNDATION Fieldbus *2 | ● | ● either H or L, or both |
● | ● Capsule Amplifier Flange (/DG1) |
● | ● |
Modbus *3 |
● | ● either H or L |
● | ● Capsule Amplifier |
- | - |
*1:In 4-20mA, output is one signal by one value。In HART, output is one signal by multiple value (up to four value).
*2:Number of output values is up to five.
*3:Flow, total flow, other temperature(flange)as output are not supported.
*4:Total flow is using HART or the pulse signal. 4-20mA signal is not supported. In FOUNDATION fieldbus, output is using IT function block.
Les produits et solutions liés
-
EJX910A
Ce transmetteur mesure avec précision la pression différentielle, la pression statique et la température du process ; il utilise ensuite ces valeurs dans un calculateur de débit embarqué hautes performances pour fournir un débit massique totalement compensé.
-
EJX930A
Conçu spécifiquement pour les applications à haute pression statique, ce transmetteur mesure avec précision la pression différentielle, la pression statique et la température du process ; il utilise ensuite ces valeurs dans un calculateur de débit embarqué hautes performances pour fournir un débit massique totalement compensé.
-
FSA120
FlowNavigator (FSA120) est un outil logiciel unique qui vous aide à tirer le meilleur parti du transmetteur multivariable EJX910A / EJX930A en prenant en charge la configuration du coefficient de décharge, du diamètre du tuyau interne en amont, du facteur de dilatation du gaz, de la densité et de la viscosité. nécessaire pour effectuer une compensation complète et un calcul dynamique du débit massique.
-
Gestionnaire des appareils de terrain mobiles (FieldMate)
FieldMate 3.0 est un outil de configuration basé sur PC qui effectue de nombreuses tâches, y compris la configuration initiale, la maintenance quotidienne, le dépannage et la sauvegarde de la configuration pour le remplacement de l'appareil.