How can the SA11 be connected to the terminals of the UM33A-S?

Please see the drawing below of the terminal arrangement of the UM33A-S.
To guarantee EMC- and Common Mode noise behavior of SA11, the FG terminal (#306) must be interconnected to Power supply Earth terminal (#112) by separate wire.
Use WU11-S type cable only, NOT WU11-V type cable. The WU11 cable can be connected directly to UM33A terminals.

UM33A-S: Terminal arrangement

Productos y Soluciones Relacionadas

  • Digital SMART SENCOM™ Adapter, SA11

    Reusable SMART adapter, requiring only the analog sensor to be disposed of when it reaches the end of its lifetime. With the SENCOM 4.0 platform, Yokogawa delivers reduced costs and waste while contributing to its long-term business goals of a sustainable future for all.

    Leer Más

Top