Base / Power supply

Base module

We offer four types of base module for 5, 9, 13 and 16 slots.

 

Power Supply module

Install one power supply module for each base module.

Details

Lineup

Name Type name Specifications
Base module*1 F3BU05-0D For power supply(F3PU20/F3PU30/F3PU26/F3PU36)+ 5 slots(CPU+I/O)
F3BU09-0N For power supply(F3PU20/F3PU30/F3PU26/F3PU36)+ 9 slots(CPU+I/O)
F3BU13-0N For power supply(F3PU20/F3PU30/F3PU26/F3PU36)+ 13 slots(CPU+I/O)
F3BU16-0N*2 For power supply(F3PU20/F3PU30/F3PU26/F3PU36)+ 16 slots(CPU+I/O)

*1:The rail mount kit must be purchased separately.
*2:This unit cannot be used with the rail mount kit.

 

Specifications

  F3BU05-0D F3BU09-0N F3BU13-0N F3BU16-0N
Number of slots 5 9 13 16
Number of I/O slots*1 4 8 12 15
Current consumption 50mA (5V DC)
Weight (g) 210g 340g 470g 550g

*1 : Number of I/O slots that can be used with a single CPU module

Lineup

Name Type name Specifications
Power supply module F3PU20-0S 100 to 240V AC,5V DC/4.3A rated output (for 5, 9, 13, and 16 slots, M4 screws)
F3PU30-0S 100 to 240V AC,5V DC/6.0A rated output (for 5, 9, 13, and 16 slots, M4 screws)
F3PU26-0S 24V DC,5V DC/4.3A rated output (for 5, 9, 13, and 16 slots, M4 screws)
F3PU36-0S 24V DC,5V DC/6.0A rated output (for 5, 9, 13, and 16 slots, M4 screws)

 

Specifications

  F3PU20-0S F3PU30-0S F3PU26-0S F3PU36-0S
Supply voltage 100-240 V AC, single phase, 50/60 Hz 24V DC
Supply voltage fluctuation range 85 to 264 V AC, 50/60Hz ±3Hz 15.6 to 31.2 V DC
Power consumption 85 VA 100 VA 33.1 W 46.2 W
Inrush current 20 A max. (120 V AC, Ta=25℃)
45 A max. (240 V AC, Ta=25℃)
20 A max.(31.2 V DC, Ta=25℃)
Rated output voltage 5 VDC
Rated output current 4.3 A 6.0 A 4.3 A 6.0 A
Insulation resistance 500 V DC 5M Ω or more between external AC terminals and  FG terminal 500 V DC 5M Ω or more between external DC terminals and FG terminal
Dielectric strength 1500 V AC for 1 minute between external AC terminals and FG terminal 1500 V AC for 1 minute between external DC terminals and FG terminal
Allowable momentary power failure time 20ms (Standard Mode) /10ms (Immediate Detection Mode) 20ms (Standard Mode) /2ms (Immediate Detection Mode)
Noise immunity Noise level:1500 Vp-p when measured by a noise simulator having a 1 μs of noise pulse width, 1ns of rise time, and 25 Hz to 60 Hz of repetition frequency
External dimensions 58(W)×100(H)×83.2(D)mm 58(W)×100(H)×126.1(D)mm 58(W)×100(H)×83.2(D)mm 58(W)×100(H)×126.1(D)mm
Weight 320g 380g 320g 410g

 

Downloads

Möchten Sie weitere Informationen über unsere Mitarbeiter, Technologien und Lösungen?

Kontakt

Top