DTSX1规格
有关详细规格,请参阅一般规格书。
项目 | 规格 |
---|---|
测量距离范围 | 2、4、6、8、10、16 km |
通道数 | 1、2、4 |
采样分辨率 | 以1米的间隔测量温度 |
温度测量时间 | 至少5秒 |
继电器输出 | 64个端口,≤35 V/1 A DC |
继电器输入 | 4个端口,12~30 V/5 mA DC |
电源电压 | 10~30 V DC |
功耗 | 30 W (环境温度为23°C时通常为15 W) |
外部尺寸 | 500 (宽)×500 (高)×250 (深)mm (注释) |
重量 | 28 kg |
注释:外部尺寸不包括突起(有关详细信息,请参阅外部尺寸图)
·火灾探测证书(EN54-22)申请中。
-
数据记录软件GA10
通过GA10软件可以建立一个无需编程的数据采集系统。GA10能够通过Modbus通信获取数据,与横河的记录器、数据记录仪、温度控制器和功率监视器实现兼容。
参考
What if you could detect signs of abnormalities in bus ducts (bus bars) quickly during maintenance and inspection work and respond to them at just the right time? Yokogawa DTSX monitoring solution constantly monitors connections that tend to deteriorate over time and contributes by pinpointing abnormality locations and reducing workload of maintenance personnel, helping to ensure stability in plant operations.
Temperature Monitoring Solution for
Quick Detection of Fires in Fume Ducts
With industrial and economic development comes increasingly large and advanced power plants and factories. Nevertheless, we find many cases where the original cables, cable tunnels, and other components of the power infrastructure have languished under continuous operation.
Recently, several ARC Advisory Group analysts and management team members had a chance to sit down with the new Yokogawa President and COO, Mr. Takashi Nishijima, and several other top Yokogawa executives to discuss the company's burgeoning presence in the worldwide upstream and midstream oil & gas industry.
下载
宣传彩页
- DTSX1光纤热检测器 (928 KB)
视频
DTSX has been increasingly used in variety of applications such as fire detection, leak detection and preventative maintenance.
想要了解更多的信息,技术&解决方案?
联系我们