Introduction
Power plant boiler houses designed to burn coal or high sulfur oil are required by Federal and State pollution regulations to "scrub" (remove) sulfur dioxide from flue gasses to meet emission limits. SO2 in flue gasses is known to be harmful to the environment, as it is one contributor to the formation of acid rain. pH control is critical for the proper functioning of the scrubber system. Flue gas desulfurization (FGD) technology, is commonly referred to as a scrubber, is proved and effective method for removing sulfur dioxide (SO2) emissions from the exhaust of coal-fired power plants.
Scrubber System
The basic principle of a sulfur dioxide scrubber system is the removal of SO2 by using its chemical characteristics to combine with water. In some cases, parallel rotating rods create a series of short throat Venturi openings. A series of low pressure, large orifice spray nozzles direct the scrubbing solution into the system. "Scrubbing liquor" is introduced into the system with the flue gas stream. Depending on the design of the scrubber, the gas can flow either concurrent (with) or counter-current (against) the scrubbing liquor. The high velocity turbulence caused by the Venturi openings ensures maximum gas to liquid contact. It is here that the droplets absorb the SO2 as well as impacting and dropping particulates out of the stream. The scrubbed gas is then sent through a demister or re-heater to prevent condensation and exhausted to atmosphere.
The scrubbing liquor can be bubbled through a slurry or either lime, Ca(OH)2, or limestone, CaCO3 and water. Either lime or limestone will combine with the sulfite ions from the flue gas to form gypsum, CaSO3. The SO2 that is captured in a scrubber combines with the lime or limestone to form a number of byproducts. A primary byproduct is calcium sulfate, commonly known as gypsum. Spent scrubbing liquids are sent to clarifier where the insoluble gypsum is removed and the water is returned to the scrubber system.
The addition of lime or limestone to scrubbing solution is controlled by monitoring the pH of the solution. Lime slurries are generally alkaline with a control point near a pH of 12 while limestone slurries are more neutral.
pH Control
A pH measurement is one of the testing methods used to monitor continuous blowdown and replenishment. The SO2 within the scrubbing gases can be controlled by maintaining the level of caustic scrubbing chemicals that are commonly used. pH is a critical factor for proper operation of a scrubber. It is also difficult to measure due to 2-15% solids and tendencies towards scaling, coating and plugging.
CaSO4 concentration decreases slightly as pH decreases. Furthermore, because the concentration of oxygen dissolved in the slurry is constant, the formation of sulfate depends only on the concentration of SO3. The precipitation of CaSO4 increases as pH decreases, thus CaSO4 is apt to form scale at a lower pH. Hard scale formation can be controlled by keeping the pH high.
The solubility of CaSO3 increases greatly as pH decreases or conversely CaSO3 forms a precipitate as pH increases. If pH is too high, "soft pluggage" occurs. Soft pluggage is due to formation of calcium sulfite precipitates which appear as large leaf like masses. Obviously maintenance of equipment that has soft pluggage is easier than with equipment that has hard scale. In many cases where soft pluggage has occurred, it can be melted off simply by lowering the pH (increasing solubility).
It is obvious that a potential dilemma exists, operation at too low pH promotes the formation of hard scale and operation at too high of a pH promotes the formation of soft pluggage. Only through experience can the proper pH range be determined. Typically limestone is added to achieve the desired level of SO2 removal based on the sulfur content of the coal, the boiler load and the monitored SO2 concentration of the flue gas, while maintaining the pH in the reaction tank at 5.5 to 6.0 pH. The pH sensor can be located in the re-circulating tank or the re-circulating line.
Conductivity Control
Conductivity one of the most common testing methods used to monitor the concentration of scrubbing chemicals and by-products. As the concentration of the scrubbing chemical is depleted, its contribution to the total conductivity value will also decrease. However, occurring at the same time, the contribution to conductivity from the by-products is increasing. Therefore, a measurable decrease in conductivity is detected as the scrubbing solution is depleted.
Difficulties can arise, however, when more than one gas is being scrubbed. Depending upon the relative proportions of the gases, the by-products formed will differ, leading to variations in the conductivity background. Although a conductivity measurement can be difficult or impossible, it may still provide a useful alarm point to alert the operator to check a grab sample. In scrubbers where the scrubbing chemical concentration is maintained by continual replenishment and blowdown, conductivity can be used to initiate blowdown to prevent high dissolved solids build-up.
In continual replacement scrubbers, conductivity can be used to initiate blowdown to prevent high dissolved solids build up. Torodial or Inductive conductivity is the best form of measurement to use in this application and the sensor should be located where it will be exposed to a representative sample.
Product Recommendations
pH Measurement System
Transmitter
FLXA21 2-wire pH/ORP measurement system
FLXA402 4-wire pH/ORP measurement system Sensor
Option 1: FU20/FU24 pH/ORP Combination electrode
Option 2: FF20 Flow-thru assembly with individual measure, reference and temperature electrodes
i.e. SM21-AG4, SR20-AP24 and SM60-T1; SC21C- AGC55 and SM60-T1
Option 3: PR10 Retractable with combination electrode Option 4: PH8EFP with PH8HS3 Holder
Conductivity Measurement System
Transmitter
FLXA21 2-wire Inductive Conductivity Analyzer
FLXA402 4-wire Inductive Conductivity analyzer
Sensor
ISC40 Inductivity Conductivity electrode with various installation options available (insertion, flow through, retractable)
行业
相关产品&解决方案
-
2-Wire Transmitter/Analyzer FLXA202
The FLEXA™ series analyzers are used for continuous on-line measurements in industrial installations. With an option for single or dual sensor measurement, they are the most flexible two-wire analyzer available.
-
Flow/NPT Fittings FF20/FS20
Yokogawa has invested considerable design and development time in producing a full range of fittings with particular emphasis on designs that reduce installation and maintenance time and consequently save operation costs.
-
FLXA202/21两线制变送器/分析仪
FLEXA™系列分析仪用于工业设施中的连续在线测量。它是灵活的两线制分析仪,可选择单传感器或双传感器测量。
-
FLXA402多通道四线制分析仪
FLEXA™系列分析仪是模块化设计的分析仪,用于在工业设施中进行连续在线测量。可提供单传感器或多传感器测量。
-
FU20/FU24/PH20一体化pH/ORP (REDOX)传感器
PH20/FU20/FU24一体化pH/ORP传感器体现了横河电机如何将“简单即好”这句格言应用于传感器技术。
-
Hot-Tap Holder PR10
On-line measurements often present extra challenges, especially when routine maintenance is required. The PR10 is ideally suitable for applications where the sensors must be removed without interrupting or shutting down the process. Without any special tools the PR10 can be retracted safely from the process at pressures up to 5 bar (72 psi). Using the PR10 allows us to place any dissolved oxygen sensor that has a PG13.5 connenction into a retractable assembly.
-
工业pH/ORP电极
pH值测量回路的关键是电极系统。横河电机研发了多种电极,确保电极系统在极其恶劣的条件下也可以运行。
-
pH和ORP传感器
pH电极和传感器是进行pH值测量的传感部分,有伸缩式、流通式、浸入式和直插式等多种安装选项。选择合适的pH电极/传感器对优化测量结果至关重要。
-
pH和ORP分析仪
pH和ORP流量计、分析仪和变送器用于pH和ORP的连续过程监测,以确保水/产品质量,如监测污水排放、批量中和、浆料存储、洗涤塔,冷却塔、化学品、水/废水处理和许多其他应用。