Introduction

The use of recycled oil as an energy source presents a significant processing problem. Because composition of the fluid is not consistent and it also may contain impurities, the use of conventional flowmeter technologies is not practical. ADMAG CA, however, has been shown to provide reliable and stable flow measurement of recycled oil containing water.

Reverse Osmosis Filter Monitoring

Reverse Osmosis Filter Monitoring 

Application

One cement producer uses recycled oil as a kiln fuel. A Coriolis mass flowmeter was used to control the recycled oil flow, however the meter readings were very unstable which made reliable control impossible. The Coriolis meter's problems were related to the separation of the oil and water as the fluid traveled the length of the meter and also the changing composition of the components (oil and water) resulted in unstable densities. In addition, the meter's zero was unstable and it was also difficult to clean the inside of the meter.

Solution

Initially, consideration was given to applying a conventional magnetic flowmeter. However, because the oil and other residuals showed a tendency to build-up in the Coriolis meter, a similar situation was expected to occur in the magmeter and the electrodes would be covered with an insulating coating. With ADMAG CA the non-wetted, capacitively coupled electrodes are immune to the effects of coating. In addition, the shorter lay length, as compared to the Coriolis meter, would better handle the potential layer separation of the oil and water.

The ADMAG CA was tested in series with the Coriolis meter. The test conditions were as follows:

Fluid Conductivity: 2.94-3.07 mS/cm
Fluid Composition: 48% oil, 43% water, 9% other
Flow Range: 0-5 tons/hr
Meter Size: 1"
Temperature: 30°C (86 deg F)
Pressure: MPa (142 psi)
Meter damping: 3 seconds

The test set-up used is in the figure above. The recorded output of the Coriolis meter shows large output fluctuations. The recorded output of ADMAG CA, however, shows the output is stable and tracks the set-point closely.

Notes

  1. Be sure to measure the conductivity of the fluid to insure that consistent values are obtained.
  2. The water content and potential water/oil separation can significantly affect the fluid conductivity. Examine a fluid sample to determine whether a two-layer separation occurs immediately or happens gradually. If separation occurs immediately, measurement even with ADMAG CA may not be possible.
Coriolis Mass Flowmeter ADMAG CA
The suspected cause for the output fluctuation is the variation in the fluid's density The ADMAG CA output is stable without large output fluctuations

ADMAG CA

ADMAG CA
ADMAG CA
  • Impervious to coating problems
  • Measures ultralow conductivity fluids to 0.01 μS/cm
  • Stable output with varying levels of oil and impurities
  • Short lay length avoids problems due to fluid separation

 

行业

  • 石油和天然气

    横河电机在石油和天然气业务的多个领域都具有丰富的经验,从离岸和陆上设施到管道、码头及深水作业。横河电机提供解决方案,提高安全性,确保准确、可靠的操作,并提高工厂效率。

    更多

相关产品&解决方案

  • 电磁流量计CA系列

    CA系列即使对于难以测量的流体(如浆料和粘附性流体)也能进行稳定的测量。基于Total Insight概念的设计提高了可操作性和可维护性。

    更多
  • 流量计

    横河电机拥有各种高质量、高精度和高可靠性的流量解决方案。凭借100多年的流量计经验,我们的技术可以为多种流量相关应用提供解决方案。

    更多
  • 电磁流量计

    横河电机在电磁流量计方面拥有几十年的经验。我们的电磁流量计可为大多数领域的工业应用提供灵活的配置。

    更多

置顶
WeChat QR Code
横河电机(中国)有限公司