Measurement of O2 Concentration in Exhaust Gases from Pulverized Coal-fired Boilers

下载 (707 KB)

Introduction

In a pulverized coal-fired boiler of a large power plant, an oxygen analyzer is essential for combustion control. Exhaust gases from the pulverized coal boiler contain a large quantity of dust and flow very fast. Oxygen analyzers that employ a sampling method may be subject to wear or clogging, resulting in increased maintenance workload and cost.

A solution to this problem is the ZR22G/ZR802G Zirconia Oxygen Analyzer that has no sampling system and utilizes a long-life sensor. A probe protector is attached to protection it against wear.

Expected Benefits

  • Improves combustion efficiency for pulverized coal-fired boilers 
  • Ensures stable, continuous oxygen measurement 
  • Reduces operating cost 
  • Minimizes the need for equipment replacement

Process Overview

While heavy oil, light oil , kerosene commonly used as a boiler fuel, coal is also used because it is inexpensive and readily available. Unlike oil, coal and gas produce a large quantity of ashes when it is burned, necessitating pulverized coal-fired boilers to be equipped with an ash removal system such as a cyclone. Exhaust gases from these boilers contain a large quantity of dust (10 to 30 g/Nm3) and flow very fast as the result of the large volume of air being blown into the boiler. For oxygen measurement in large ducts, a probe with a long insertion length is used.

Pulverized Boiler

Solution Details

Field Data

Process conditions

Measurement point Economizer outlet
Temperature 300 to 400°C
Flow rate ≤ 30 m/s
Pressure ±1.5 kPa
Dust approx. 15 g/Nm3 or less
Fuel pulverized coal

Measurement system

Detector ZR22G-☐☐☐-S-☐-☐-☐-☐-E-A/CV
Probe protector ZO21R-L-☐☐☐-☐*B
Converter ZR802G-☐-☐-N-N /☐
Flow setting unit ZA8F-☐*C
Pressure regulator G7013XF or G7014XF
Case for calibration gas cylinder E7044KF

Note: the calibration gas cylinder must be purchased locally

Utilities

Rated voltage 100 to 240 V AC
Rated frequency 50/60 Hz
Power consumption 330 VA (Max. 800 VA)
Instrument air 300 to 700 kPa

ZR802G

Notes

  • A probe protector should be attached to the probe for protection against wear or damage. The probe protector should be mounted with the notch of the probe head pointing downstream in the gas flow.
  • It is recommended that the detector be installed with the probe tip pointing downward. As shown in the figure, it may be installed horizontally, too. The probe head tip should not point upstream in the gas flow.

行业

  • 火电

    使用煤、石油或天然气作为燃料的火力发电占发电量的大部分。

    更多
  • 电力

    在20世纪70年代中期,横河电机发布EBS电子控制系统,从而正式进入电力行业。从那时起,横河电机一直坚持不断发展技术和能力,旨在为客户提供更好的服务和解决方案。

    横河电机凭借着电力解决方案网络,在充满活力的电力市场中发挥着积极的作用。通过结合资源和行业知识,使得团队合作更加紧密。横河电机的电力专业人员们将携手合作,为客户提供适合其复杂要求的解决方案。

    更多

相关产品&解决方案

  • Zirconia Oxygen/Humidity Analyzer ZR22G, ZR802G

    This Oxygen concentration and humidity at high temperatures consists of a ZR22G detector equipped with a long-life and highly reliable zirconia sensor, and a converter ZR802G equipped with digital communication and data log functions.
    ZR22G and ZR802G can be measured directly and continuously without a sampling device. It is easy to maintain and reduce operating costs by self-diagnosis of sensor deterioration (without using calibration gas )and replacing the heater assembly on site.

    更多