Can I write MELSEC data on the DX2000 via Modbus/TCP communications?

Yes. However, the DX2000 requires the MATH function option (suffix code: /M1).
The procedure is as follows.

  1. Enable the DX2000's Modbus server function.
  2. Register communication input channels (C01 or C02) in a formula and start the MATH function.
  3. Next, assign MATH channels to groups, and set them up to display screens.
  4. On the MELSEC side, write to the DX's hold registers (communication input channels). The register addresses for the DX's communication input channels are 400001 and higher.

For information on registers, see the DX2000's "Communication Interface User's Manual. " It includes a list of registers. For information on MELSEC operation, see the MELSEC operation manual.
DX2000 user's manual

 

Related Products & Solutions

  • DX1000 / DX2000 с кнопочным управлением

    Серия Daqstation DX1000 / 2000 представляет собой систему сбора данных с экраном отображения данных. Интерфейс регистратора поддерживает пользовательскую графику для отраслевых приложений, журнал аудита и имеет расширенную безопасность к доступу данных в соответствии с требованиями FDA 21 CFR, Part 11.

    Узнать больше