I'm writing PID settings via CC-Link communication, but when I send 100 to proportional band P, 10.0 appears on the main unit.

Proportional band P has data of up to 1 decimal point. By contrast, communication data has no decimal point. If you want to write 100.0% to P, send 1000. For differential and integral time, the data has no decimal point.