There's no output with an isolator. What should I do?

  1. Check the power supply wiring.
  2. Check whether the power supply voltage meets the specifications.
  3. Check the polarity of the input wiring.
  4. Use a tester to measure the input terminal voltage.
  5. For current input specifications, confirm that the accessory resistor is connected to the input terminal (applies to the VJ and M series).
  6. If the output signal is of the current specifications, attach an external 250 Ω resistance and measure the voltage.

Related Products & Solutions

  • JUXTA VJ Series Limit Alarms

    The VJ series limit alarms are compact, plug-in type alarm setting devices with easy-to-use functions. Four models are available: the VJAK for 2-wire system transmitters; the VJHK with DC voltage/DC current inputs; the VJRK with RTD inputs; the VJTK with thermocouple inputs; and the VJUK with universal inputs.

    See More
  • JUXTA VJ Series Signal Conditioners

    Compact size, plug-in style and microprocessor based high performance capabilities (Multi-function types) makes the VJ Series Signal Conditioners an excellent choice for almost every application. Analog output, Hi-Low alarm relay outputs or RS-485 MODBUS communication is available as optional second output.