For power monitors, you need to set up CT and VT ratios. (In the case of the PR300 power monitor, phase, wiring method, voltage range, and other settings are required in advance.) However, even when you enter these settings, there are times when the measured values differ significantly from the actual values. In such cases, check the active power (W). It can be negative, or smaller than actual. (When the active power display is negative, this indicates that power is being supplied (regenerated energy) to the power supply from the load.) In this case, recheck the current/voltage input wiring, and the orientation and phase of the attachment of the CT.
Related Products & Solutions
-
Power monitoring package SMARTDAC+ GM / UPM100
Power monitoring package SMARTDAC+ GM/UPM100 is a data collection system for energy saving monitoring consisting of 920 MHz compatible power monitor UPM 100 and data acquisition system GM. Easily visualize the electric power used in the factory (graph) and create reports, etc. We can help waste energy by finding waste of electricity used.
-