I perform auto-tuning on the UT, but the auto-tuning parameters (AT) do not appear.

Check the following.

  1. Is the control type (CNT) ON/OFF, or 2 position 2 stage control?--> If so, change it to something other than that.
  2. Is the STOP lamp lit? --> Start operation (RUN).
  3. Is the MAN lamp lit? --> Set it to AUTO.

 

Related Products & Solutions

  • Advanced Application UT75A

    The UT75A temperature controllers employ an easy-to-read, 14-segment large color LCD display, along with navigation keys, thus greatly increasing the monitoring and operating capabilities. A ladder sequence function is included as standard. The short depth of the controller helps save instrument panel space. The UT75A also support open networks such as Ethernet communication.

    See More
  • Mid-level UT55A/UT52A

    The UT55A and UT52A temperature controllers employ an easy-to-read, 14-segment large color LCD display, along with navigation keys, thus greatly increasing the monitoring and operating capabilities. A ladder sequence function is included as standard. The short depth of the controller helps save instrument panel space. The UT55A/UT52A also support open networks such as Ethernet communication.

    See More
  • UT32A-D

    The UT32A-D is a compact digital indicating controller with selectable 2-loop control. It also includes a ladder sequence function.

    See More
  • UT35A/UT32A

    The UT35A and UT32A temperature controllers employ an easy-to-read, 14-segment large color LCD display, along with navigation keys, thus greatly increasing the monitoring and operating capabilities. A ladder sequence function is included as standard. The short depth of the controller helps save instrument panel space. The UT35A/UT32A also support open networks such as Ethernet communication.

    See More

Top