VA500
Hinweis: Dieses Produkt wurde eingestellt am

Publikationen

Stop monitoring and recording on DAQLOGGER, then perform steps 1 to 3. On GateMX/MW, click the Acquire button of the corresponding MW100 to get the MW100's information. In DAQLOGGER manager, use "ENVI" on the Gate to perform automat...
Yes, an inexpensive release upgrade kit is available.
Files can be automatically divided by number of data, day, or hour. Also, with the latest versions (R7.08 or later), files can be divided by month.
Ethernet, RS-232C, and RS-422A/485.
The following shows you how to assign 2 instances of Gate to DAQLOGGER. Launch GateDX-P, then click the ENVI button in DAQLOGGER manager. After GateDX-P starts, click the ENVI button in DAQLOGGER manager. Assign 2 Gates Click the address field o...
It is the DAQLOGGER time, in other words, the time on the PC.
Use the latest version of SMARTDAC+ Standard Universal Viewer.
When logging in DAQLOGGER, “LackData” appears in the logs if some data is missing, and “num” is the number of missing data.
With DAQWORX programs, even if the licenses are different, you cannot run multiple instances of the same software on the same OS. If using two GateMODBUS licenses, please use two different PCs, configuring them as follows. 1st PC: GateMODBUS,DAQLOGGE...
When data files are being recorded, the OS prevents them from being accessed by other software. If DAQLOGGER attempts to write to a file being copied, it will be prevented from doing so. Do not copy files being recorded.
You can create them with the Report function, but you cannot print them out.
Check the number of data and tags. Excel's maximum worksheet size is 65536 rows by 256 columns. Set it up so that the number of data along the time axis is 65536 or less, and the number of tags is 250 or less.
How can I output an alarm beep on DAQLOGGER?
(ns-faq-daqworx-13022-spec)
Open the alarm window, then check Alarm sound in the Monitor menu.
Can I send alarm occurrences via e-mail?
(ns-faq-daqworx-13008-spec)
Yes. Set this up in the event processor.
Can I connect multiple products to DAQLOGGER?
(ns-faq-daqworx-13007-spec)
Yes. Up to 32 units can be connected.
Can I connect with Modbus instruments?
(ns-faq-daqworx-13006-connect)
By using GateModbus, you can acquire data from Modbus devices on DAQLOGGER.
MX100 → GateMX/MW or MXLOGGER → DAQLOGGER DA100 → DAQLOGGER with the above you can load both data on DAQLOGGER, but it will take at least one second.
Yes. Use the remote controller function.
Generally, the recording functions differ as follows. On DAQLOGGER, data from multiple products is acquired and recorded together at the time of the PC, so it has a degree of synchronicity. With DAQEXPLORER, files are recorded at the time on the ...
The TAG numbers cannot be changed. They are fixed from TAG0001 to TAG1600. The TAG comment can be up to 16 half-width alphanumeric characters, and the GR name can be up to 8.
3600. Data beyond that are invisible.
Yes, you can if you use the DAQLOGGER client.
After you start scanning, you have to start logging too. After you start logging, the files will start to be created at the specified date/time.
Unfortunately you will need to stop DAQLOGGER. When you rescan, the changed alarm values will apply.
No. Consider the GA10 Data Logging Software. The GA10 can connect with DAQLOGGER. For details, see GA10 General Specifications (GS 04L65B01-01EN) "Connectable Devices and Software". ...
When viewing MXLOGGER from DAQLOGGER, the MXLOGGER data is distinguished by the MXLOGGER system number. The system number is set automatically according to the MX scan interval and unit. When specifying an MXLOGGER on DAQLOGGER, if you specify a syst...
Yes, by using GateµR along with DAQLOGGER.
If DAQLOGGER stops while communicating with the DX1000, depending on the timing, the DX1000 might enter a response wait state and be unable to receive any other commands. With apologies, please turn OFF the DX1000 and restart DAQLOGGER.

Möchten Sie weitere Informationen über unsere Mitarbeiter, Technologien und Lösungen?

Kontakt

Top