Refinery Wastewater: Oil & Grease Removal

다운로드 (288 KB)

Background Information

Removal of free oil and grease from a wastewater stream reduces the potential for equipment problems to occur further downstream. There are three forms of oil encountered in wastewater treatment at a refinery. They are:

  1. Free Oil or floating oil is removed by either skimming the surface in the skim tank or by gravity separation in the API separator.
  2. Emulsified Oil is comprised of oil droplets in stable suspension within the wastewater. Removal requires chemical addition to lower the pH followed by addition of dissolved oxygen or nitrogen to remove the emulsified oils as they break free from the wastewater.
  3. Dissolved Oil is a true molecular solution within the water and can only be removed with biological treatment.

Figure 1 shows a typical biological wastewater treatment schematic; however other treatment options do exist as well. Biological treatment systems are commonly used for "normal" industrial oily wastewaters streams, and can also be used to treat sanitary waste. A disadvantage is the difficulty sustaining the biomass environment due to high swings in wastewater concentrations, TDS and temperature.

wastewater-system

Introduction


api-seperatorsAPI Separators: API or American Petroleum Institute Separators are normally the first and most important step in a refineries wastewater treatment. It uses the differences in oil and water's specific gravity to filter out the majority of free oil within the mixture. The lighter oils will remain at the top of the liquid and can be skimmed off, while the heavier oil will settle to the bottom.

The above figure shows a detail drawing of a typical API separator. A conventional oil-water separator contains a conveyor to assist in the separation of the heavier oils and grease, a scraper/skimmer and a baffle.

pH is typically measured at the outlet as an indicator of potential problems, such as flocculation, in the secondary treatment. It is important to note that because emulsified oil is still present in the water mixture, coating will occur causing a sluggish reading.

At this point in the treatment process the emulsified oil is still in soluble form. The removal of the emulsified oil requires either a chemical addition to lower the pH or use of emulsion breakers.

Dissolved/ Air Flotation: Once treated, the wastewater often enters an air flotation unit to remove the emulsified oil as it begins to break free from the wastewater, using dissolved oxygen or nitrogen.

Bioreactors (Activated sludge treatment): At this phase the wastewater still contains dissolved oil in a true molecular form. The only way to remove the remaining dissolved oil is thru biological treatment. This and the remaining steps are the same as those found in a normal wastewater treatment facility.

Many components in the process must be in balance in order to obtain complete synergy such as, biomass blends, air, return activated sludge (RAS), waste activated sludge (WAS) and throughput. It is essential to monitor and control all factors which influence the efficiency of the biological conditions in the basin; for example:

Temperature: Most biomass achieves optimum efficiency in a temperature range between 10-40°C. Increasing or decreasing the temperature can result in the increasing or decreasing the rate at which the bugs eat and reproduce. All chemical reactions taking place are affected by the process temperature as well.

pH: For most systems the pH should be kept between 6.5 to 8.5 pH, when the pH is too high or too low, the biomass loses the ability to convert the food to energy and raw materials. A pH below 6.5 may cause growth of fungi and fungal bulking, and will have to be adjusted using a caustic, lime or magnesium hydroxide.

Low Nutrients: If nitrogen and phosphorus are not present in sufficient amounts it can limit the growth rate of the biomass. A sign of nutrient deficiency includes foam on the aeration basin.

Dissolved Oxygen: DO is a critical measurement and will be maintained between 1-3 mg/L. The concentration is an indication of the basin environment; whether it is in denitrification (excess nitrate, NO3) or nitrification (excess ammonium, NH4) environment. Essentially the DO measurement is used to minimize ammonium breakthrough. It is not uncommon to see NH4 and DO measurements together.

Septicity/Toxicity: Septic wastes contain elevated amounts of sulfides and organic acids (such as acetic acid).Other organic materials and heavy metals are also toxic to the biomass, reducing their efficiency or even destroying them.

Summary

Maintaining proper pH measurements upstream and decrease problems seen downstream.

업종

  • 정수 및 하수 처리

    Yokogawa는 보다 효율적인 사회를 만들기 위하여 에너지 최적화 기술 개발, 온실가스 감축, 오염 물질로부터 환경을 보호하는 견고한 제품 제작 등을 통해 지속 가능한 수자원 생산을 위한 제어 솔루션을 제공하고 있습니다. Yokogawa의 첨단 기술과 폭넓은 애플리케이션 노하우를 통해 고객과 협력하여 사업을 활성화하고 플랜트 수명주기 전반에 걸쳐 높은 가치를 제공할 수 있는 지속 가능한 솔루션을 제공합니다. 당사의 기술과 제품은 플랜트의 성능을 향상시키고 오늘날의 수자원 시장에서 경쟁적으로 운영할 수 있도록 보장하며 운영비를 절감합니다. Yokogawa는 지자체 및 공업용수 처리 시장에서 광범위한 수처리 응용 분야를 지원합니다.

    See More

Related Products & Solutions

  • 2-Wire Transmitter/Analyzer FLXA202

    The FLEXA™ series analyzers are used for continuous on-line measurements in industrial installations. With an option for single or dual sensor measurement, they are the most flexible two-wire analyzer available.

    See More
  • Digital SMART SENCOM™ Adapter, SA11

    Reusable SMART adapter, requiring only the analog sensor to be disposed of when it reaches the end of its lifetime. With the SENCOM 4.0 platform, Yokogawa delivers reduced costs and waste while contributing to its long-term business goals of a sustainable future for all.

    See More
  • Measuring Sensor DO30G

    용존산소용 DO30G 센서는 하수처리장, 유출활성 슬러지 공정 및 음용수 처리와 같은 수처리 설비에서 사용하도록 설계되었습니다. 또한 하천 감시, 섭취 보호, 양식장 및 수질이 중요한 분야에도 효과적입니다. 

    See More
  • Dissolved Oxygen Sensors

    용존 산소 (DO) 전극과 센서는 DO 측정의 감지 부분입니다.

    용존 산소 측정에는 세 가지 일반적인 기술이 있습니다. : 폴라로그래픽, 갈바닉 및 옵티칼 

    Floating ball, Retractable, Flow-though, 침적 및 직접 삽입을 포함한 다양한 설치 옵션이 있습니다.

    See More
  • SENCOM™ SMART Digital Sensors

    디지털 또는 SMART 센서는 센서의 통합 부분 인 통합 칩에 특정 측정 및 교정 데이터를 유지합니다. 이 데이터는 SPS24와 같은 데이터 관리 소프트웨어를 사용하여 센서와 프로세스 트랜스미터 또는 실험실 PC간에 교환 할 수 있습니다.

    See More

Top