Testing Performance Specifications
| Model |
Rating |
Effective
Measuring Range |
AC Voltage
Measuring Range |
| MY10-01 |
125V/20MΩ |
0.01 to 20MΩ |
0 to 250V |
| MY10-02 |
250V/50MΩ |
0.01 to 50MΩ |
0 to 300V |
| MY10-03 |
500V/100MΩ |
0.05 to 100MΩ |
0 to 500V |
| MY10-04 |
500V/1000MΩ |
0.5 to 1000MΩ |
0 to 500V |
| MY10-05 |
1000V/2000MΩ |
1 to 2000MΩ |
0 to 500V |
- Scale length:
Approx. 107 mm; afterglow-illuminated scale plate
- AC voltage measurement:
If any AC voltage is present across the test terminals, the tester lets you know by pointing to an AC voltage value and turning on the LED lamp. You can perform AC voltage measurement with the MEAN switch turned off.
- Additional functions:
Automatic discharge function:
- If the object under test remains electrified after the MEAS switch is turned off, the tester lets you know by turning on the LED lamp. If you leave the tester connected to the electrified object, the tester automatically begins to discharge electricity and then goes out.
- When the object under test is capacitive and electrified, the tester lets you know by turning on the LED lamp. When left connected to the object, the tester automatically discharges electricity, thus preventing possible electric shock or spike noise at power-on.
- Battery check:
(BAT mark on the scale plate)
- Battery life:
Approx. 10 hours when continuously operated on manganese-oxide batteries with the pointer pointing to the central scale value.
- Batteries:
Four AA (R6P) batteries
- Dimensions:
Approx. 125 (W) × 103 (H) × 53 (D) (mm), excluding protrusions
- Weight:
Approx. 500 g (main unit and batteries only, excluding accessories)
- Compliance:
EN61010-1:1993; EN61010-2-31:1995 (Over voltage Category III, Pollution Degree 2 installations for indoor use)
|