- Measuring Range:
| Insulation Resistance |
:
|
500V/100MΩ (320731), 250V/50MΩ (320732)
|
| Earth Resistance |
:
|
0 to 15/150/1500Ω
|
| Earth Voltage |
:
|
0 to 30V AC
|
| AC Voltage |
:
|
70 to 130/140 to 260/ 280 to 520V AC
|
| AC Current |
:
|
0 to 15/30/75/150/300A AC
|
- Accuracy:
| Insulation Resistance |
:
|
±5% of indicated value within effective
measuring range except zero and rated value, ±10% of rated
value for rated resistance, ± 0.7% of scale length at zero
and infinity
|
| Earth Rresistance |
:
|
±3% of full scale
|
| AC Voltage |
:
|
±1.5% of full scale
|
| AC Current |
:
|
±2.5% of full scale
|
- Power Source:
Eight 1.5V batteries (IEC R6P, ANSI AA, Mignon 1.5V or equivalent)
- Accessories supplied at no extra cost:
1.5V batteries (8 pcs, built-in), measurement leads (1 pair for insulation resistance and AC V measurements), measurement leads (3pcs, for resistance measurement), clip-on current transformer (1pc), accessory case (1pc), carrying case (1pc)
|