Parameter
|
Specification
|
|
Method of detection
|
Mean value
|
|
Display
|
LCD(Digital display:3999 counts)
|
|
Response Time
|
Approx. 2 seconds
|
|
Range Switching
|
Manual-range(on AC current range)/
Auto-range(on AC/DC voltage range, resistance range)
|
|
Data Hold
|
On all range
|
|
Peak Hold
|
On AC current range
|
| Ambient temperature and humidity |
0 to 40 deg.C, 85% RH or less (no condensation)
|
|
Temperature Coefficient
|
-
|
|
Influence of external magnetic field
|
1A or less at 400A/m
|
|
Influence of conductor position
|
±(2.0% rdg + 3dgt) or less
|
|
Safety Standard
|
Conforms EN61010-1, EN61010-2-031, EN61010-2-032
|
|
Circuit Voltage
|
1000Vrms or less
|
|
Withstanding Voltage
|
5.55kV AC for one minute
|
|
Power Supply
|
R6P(SUM-3) ×2 or LR6 ×2
|
|
Battery Life
|
Approx. 150 hours (continuous)
|
|
Consumed Current
|
Approx. 5mA
|
|
Sleep Function
|
Automatically powered down in about 10 minutes after the last switch operation
|
|
Diameter of measurable conductor
|
54mm at maximum
|
|
Dimensions
|
Approx. 105(W) × 247(H) × 49(D)mm
|
|
Weight
|
Approx. 470g
|
|
Accessories
|
User's manual(IM CL150), batteries,
carrying case(93034)
|